Télécharger Imprimer la page

Franklin Electric SUBDRIVE CONNECT Serie Manuel Du Propriétaire page 46

Publicité

Les langues disponibles

Les langues disponibles

MAINTENANCE
Troubleshooting
Symptom Based Troubleshooting
T T a a b b l l e e 2 2 . .
Display
Condition
None
Green
"—"
No water
Red Fault
Codes
Green Motor
Frequency
Pressure Fluc-
Green Motor
tuations (Poor
Frequency
Regulation)
Run On
Green Motor
(pump won't
Frequency
stop)
Runs But
Flashing Red
Trips
Green Motor
Low Pressure
Frequency
46
Possible Cause
No supply voltage present
Display board cable discon-
nected or loose
Pressure sensor circuit
Fault detected
Incorrect motor or pump
settings
Loose switch or cable
connection
Motor may be running
backwards
Gulping water at pump inlet
Frequency max and amps high
Frequency max and amps er-
ratic with dragging impellers
Pressure sensor placement
and setting
Pressure gauge placement
Pressure tank size and
precharge
Tank may be too small for sys-
tem flow
Leak in system
Air in pump intake (lack of
submergence)
System response setting
Pressure sensor placement
and setting
Tank pre-charge pressure
Impeller damage
Leaky system
Sized improperly (pump can't
build enough head)
A fault has occurred
Pressure sensor setting, pump
rotation, pump sizing
High temperature
Corrective Action
Verify cable connection between Power Board and Control Board
If correct voltage is present, replace drive
Verify water pressure is below system set point
If Pressure Input Board break-away tab is removed, ensure auxiliary de-
vice is connected and closed circuit
Jumper wires together at pressure sensor; if pump starts, replace sensor
If pump doesn't start, check sensor connection at Pressure Input Board;
if loose, repair
If pump doesn't start, jumper sensor connection at Pressure Input Board.
If pump starts, replace wire
If pump doesn't start with sensor Pressure Input Board connection jum-
pered, replace Pressure Input Board
If pump doesn't start with new Pressure Input Board, replace
Refer
to"Diagnostic Fault Codes" on page 43
Verify Maximum Frequency setting. If this setting was reduced below
maximum value, increase
Verify motor/pump ratings and match to motor/pump settings on drive
(DIP switch or Wi-Fi)
Verify motor connections
Frequency max, amps low, check for closed valve, or stuck check valve
Check all piping connections
Disconnect power, allow well to recover, and restart
Check for hole in pipe
Check pump operation and for dragging impellers
Correct pressure sensor placement and settings
Disconnect power and check pressure gauge for drop
Set deeper in the well or tank. Install a flow sleeve with airtight seal
around drop pipe and cable
If fluctuation is only on branches before sensor, enable Steady Flow
Change tank size configuration
Reduce frequency output range
Adjust System Response value
Check frequency at low flows. Pressure setting may be too close to
pump max head
Verify precharge at 70% if tank size is larger than minimum. Increase
precharge (up to 85%).
Verify that the system will build and hold pressure
Enable bump and/or aggressive bump
Increase minimum frequency
Proceed to fault code description and remedy
Adjust pressure sensor, check pump rotation.
Check frequency at max flow, check max pressure
High ambient and/or drive temperature will cause drive to foldback
power and run with reduced performance
.

Publicité

loading