Télécharger Imprimer la page

Franklin Electric SUBDRIVE CONNECT Serie Manuel Du Propriétaire page 44

Publicité

Les langues disponibles

Les langues disponibles

MAINTENANCE
Troubleshooting
T T a a b b l l e e 1 1
( ( c c o o n n t t i i n n u u e e d d ) )
Codes
Fault
F F 6 6
Short Circuit
F F 7 7
Overheated Drive •
F F 8 8
Overpressure
F F 9 9
Internal PCB
Fault
F F 1 1 2 2
Overvoltage
F F 1 1 4 4
Broken Pipe
F F 1 1 5 5
Phase Imbalance •
F F 1 1 6 6
Ground Fault
F F 1 1 7 7
Inverter
Temperature
Sensor Fault
F F 1 1 8 8
PFC
Temperature
Sensor Fault
F F 1 1 9 9
Communication
Fault
F F 2 2 2 2
Display/Wi-Fi
Board Expected
Fault
F F 2 2 3 3
Main Board Start-
up Fault
44
Possible Causes
When fault is indicated immediately after
power-up, short circuit caused by a shorted
connection, defective cable, splice, or motor
Amperage exceeded 25 amps on DC test at
start or SF amps during running
Incorrect output wiring, phase to phase
short, phase to ground short in wiring or
motor
High ambient temperature
Direct sunlight
Obstruction of airflow channel
Fan blocked or inoperable, ambient above
122 °F (50 °C)
System pressure exceeded pressure setpoint
by the overpressure offset (30 PSI default)
A fault was found internal to drive
High line voltage
Internal voltage too high
Broken pipe or large leak is detected in the
system
Drive runs at full power for 10 minutes with-
out reaching pressure setpoint
Large water draw, such as a sprinkler system,
does not allow system to reach pressure
setpoint
Motor phase currents differ by 20% or more.
Motor is worn internally
Motor cable resistance is not equal
Incorrect motor type setting (single- or
three-phase)
Motor output cable is damaged or exposed
to water
Phase to ground short
Internal temperature sensor is
malfunctioning
Cable connection between Control Board and
Power Board is loose or disconnected
Internal circuit failure
A fault was found internal to drive
Corrective Action
Check wiring and fix as necessary
If fault is present after resetting and removing motor
leads, replace drive
Wait until drive temperature drops below 194 °F (90 °C)
to restart
Replace fans or fan module; or relocate drive as necessary
Remove debris from fan intake/exhaust
Remove and clean optional air screen kit (if installed)
System will restart when system pressure drops below
pressure setpoint and drawdown setting.
Adjust pressure transducer location.
Adjust pressure tank precharge or sizing.
Adjust system response.
Contact your Franklin Electric Service Personnel
Unit may require replacement. Contact your supplier.
Check incoming power connections and correct or tighten
terminals if necessary
If line voltage is stable and measured below 260 VAC and
problem persists, contact your Franklin Electric Service
Personnel.
Check system for large leak or broken pipe
If the system contains a sprinkler system or is being used
to fill a pool or cistern, disable the Broken Pipe Detection.
Check resistance of motor cable and motor windings.
Verify motor type matched drive settings (single- or
three-phase)
Check motor cable insulation resistance with megger
(while not connected to drive). Replace motor cable if
needed.
Contact your Franklin Electric Service Personnel
If problem persists, unit may require replacement. Contact
your supplier.
Check cable connection between Display/Wi-Fi Board and
Main Control Board.
If problem persists, unit may require replacement. Contact
your supplier.
Contact your Franklin Electric Service Personnel
Unit may require replacement. Contact your supplier.

Publicité

loading