T T a a b b l l e e 1 1
( ( c c o o n n t t i i n n u u e e d d ) )
Codes
Fault
F F 2 2 4 4
Invalid DIP
Switch Setting
F F 2 2 5 5
Moisture Sensor
Fault
F F 2 2 6 6
Aux Input Fault
F F 2 2 7 7
Pressure
Transducer
Error
F F 2 2 8 8
Real Time Clock
Fault
F F 4 4 1 1
Duplex
Alternator
Sensor Mismatch
F F 4 4 2 2
Duplex
Alternator
Firmware
Mismatch
F F 4 4 3 3
Duplex
Alternator
Comm Fault
F F 4 4 4 4
Duplex
Alternator
Unexpected
Comm
F F 4 4 5 5
Duplex
Alternator
Demand
Fault
Power down, disconnect leads to the motor and power up the SubDrive:
If the SubDrive does not give an "open phase" fault (F5), then there is a problem with the SubDrive.
Connect the SubDrive to a dry motor. If the motor goes through DC test and gives "underload" fault
(F1), the SubDrive is working properly.
Possible Causes
No DIP Switch set or more than one (1) DIP
Switch set for Motor and/or Pump size
Invalid combination of DIP switches for drive
type (SD or MD mode), Motor hp, and Pump
hp.
Moisture Sensor has detected moisture or
water
External device wired to the WET SENSOR
terminal has satisfied the configured fault
condition
Input is incorrectly configured
External device wired to the AUX IN terminal
has satisfied the configured fault condition
Input is incorrectly configured
Pressure transducer has failed
Pressure transducer is incorrectly wired
Pressure transducer signal is outside of the
expected range
Pressure transducer is being used but DIP
SW1 Position 5 is in the UP position
Pressure Sensor is being used but SW1 Posi-
tion 5 is in the DOWN position
Internal real time clock is not programmed
Real time clock battery on Control Board is
loose
Real time clock battery is dead
Drives using the built-in Duplex Alternator
function are configured with pressure sensor
types that do not match
Drives using the built-in Duplex Alternator
function have firmware versions that are not
matched
Improper Duplex Alternator cable connection
Duplex Alternator cable is damaged
Duplex Alternator cable is installed but Du-
plex Alternator function is only configured
on one drive
Drives are incorrectly configured
Both drives are running and unable to satisfy
the Primary Setpoint pressure
Corrective Action
Check DIP switch settings
Check Moisture Sensor location for moisture or presence
of water. Clean and dry area. If drive is stopped, power
must be cycled to clear the fault.
Ensure Moisture Sensor input is configured correctly
Ensure the Auxiliary Input is configured correctly
Replace pressure transducer
Check pressure transducer wiring connections
Ensure DIP SW1 Position 5 is in the correct position for the
sensor type being used (DOWN for pressure transducer,
UP for pressure switch)
Ensure battery is properly inserted. If corrected, reconnect
to drive using mobile app to reset the internal clock time
Replace battery. If replaced, reconnect to the drive using
the mobile app to reset the internal clock time
Ensure the drives using the built-in Duplex Alternator
function have matching pressure sensor types, either a
traditional pressure sensor or a pressure transducer.
Make sure the transducers are both PSI type or bar type,
if both drives are configured with a pressure transducer.
Update the firmware version of one or both drives to a
matching firmware version using the FE Connect mobile
app.
Check Duplex Alternator cable connections
Replace Duplex Alternator cable
Complete Duplex Alternator configuration on both drives
Ensure both drives are configured properly. One drive
must be configured as Pump 1, the other drive must be
configured as Pump 2, and the Switching Interval must
match.
Inspect each system for proper pump operation
MAINTENANCE
Troubleshooting
45