Télécharger Imprimer la page

Franklin Electric SUBDRIVE CONNECT Serie Manuel Du Propriétaire page 21

Publicité

Les langues disponibles

Les langues disponibles

ELECTRICAL INSTALLATION
Wiring Guidelines
NOTICE
Risk of damage to VFD, or malfunction can occur.
Follow all wire routing and grounding instructions carefully. Inductive currents caused by parallel
wiring, or close proximity between high voltage and control wiring can cause unexpected
behaviors.
Do not run input power and motor wires in the same conduit.
Do not run motor wires from multiple VFDs in common conduit.
Do not run control wiring parallel with high voltage wiring.
Do not run VFD wiring parallel with building or facility wiring.
Do not use aluminum wires for VFD connections.
Do not run any wiring through the airflow channel in the back of the drive.
Do not install a magnetic contactor or disconnect in the motor circuit.
Do not use with a Ground Fault Circuit Interrupter (GFCI).
Do not leave wire fragments, metal shavings or other metal objects inside the VFD.
Improper splicing or damage to motor cable insulation may expose the conductor(s) to moisture
and can produce motor cable failure.
For retrofit application, check the integrity of power and motor leads. This requires measuring the
insulation resistance with a suitable megohm-meter.
Cable Routing
Use the following diagram as a guide when routing wiring to VFD.
IMPORTANT: All control wiring—sensors, switches, transducers, etc.—should be in a separate conduit
routed individually, not parallel, from high voltage wiring. In addition, any shielded cables should be
properly grounded.
1.
Mount the drive as close as possible
to the service entrance panel. Wire
directly to the service entrance. Do
not connect to a sub-panel.
2. Use a dedicated branch circuit for
the drive. Refer to
Protection" on page
3. Route motor wiring out of building
as soon as possible to reduce the
chance of EMI or electrical interfer-
ence on the motor cables. Separate
input power and motor wiring by at
least 8 inches (20.3 cm). Refer to
"Output (Motor) Wire Sizing" on
page
22.
4. Cross over other branch circuits and
facility wiring at a 90° angle. If it is
necessary to run wiring in parallel,
separate by at least 8 inches (20.3
cm).
"Branch Circuit
22.
ELECTRICAL INSTALLATION
Wiring Guidelines
21

Publicité

loading