MAINTENANCE
Troubleshooting
System Diagnostic Fault History
The SubDrive Connect continuously monitors system performance and can detect a variety of abnormal
conditions. In many cases, the drive will compensate as needed to maintain continuous system opera-
tion; however, if there is a high risk of equipment damage, the drive will stop the system and display the
fault condition. If possible, the drive will try to restart itself when the fault condition subsides. Each time
a fault is detected in the system, the drive records the fault with the date and time the fault was de-
tected. A maximum of 500 events are recorded and can be viewed and emailed using the FE Connect
mobile app.
Refer to
"Communications" on page
Diagnostic Fault Codes
T T a a b b l l e e 1 1 . .
Codes
Fault
F F 1 1
Motor
Underload
F F 2 2
Undervoltage
F F 3 3
Overcurrent or
Locked Pump
F F 4 4
Incorrectly Wired •
F F 5 5
Output Open
Phase
41.
Possible Causes
High static, light loading pump
Over-pumped well
Broken shaft or coupling
Blocked screen, worn pump
Air/gas locked pump
SubDrive not set proerly for pump end
Frequency near maximum with load less than
configured underload sensitivity
System is drawing down to pump inlet (out
of water)
Maximum frequency set too low for perma-
nent magnet motor
Low line voltage, less than approximately
150 VAC
Miswired input leads
Loose connection at breaker or panel
Motor and/or pump misalignment
Dragging motor and/or pump
Motor and/or pump locked
Abrasives in pump
Excess motor cable length
Amperage above SFL at 30 Hz
Incorrect motor type selected
Wrong resistance values on main and start
Loose connection
Defective motor or drop cable
Wrong motor
Corrective Action
Reset Potentiometer for less sensitivity if not out of water
Check pump rotation, reconnect if necessary for proper
rotation
If possible, set deeper in well to reduce possibility of air/
gas locked pump
Verify DIP switches are set properly
Check Underload Sensitivity Setting (Potentiometer or
Wi-Fi)
Increase maximum frequency to 125Hz or more for perma-
nent magnet motors - if maximum frequency must be be-
low 125Hz, adjust underload sensitivity setting to a lower
value.
Line voltage needs to be 190 to 260 VAC
Check incoming power connections and correct or tighten
if necessary
Correct incoming voltage. Check circuit breaker or fuses,
contact power company
Remove and repair or replace as required
Reduce motor cable length. Adhere to Maximum Motor
Cable Length table.
Confirm the motor type on DIP SW1 Position 7 is set
correctly.
Check wiring, motor size and DIP switch setting. Adjust or
repair as needed
Open reading on DC test at start.
Check drop cable and motor resistance, tighten output
connections, and repair or replace as necessary.
Use dry motor to check drive functions. If drive runs and
exhibits an underload fault, drive is good.