5.1.3 Isolator switch
ON
5.2 Operating states
With the ISOLATOR switch in ON you give the electrical power no the
unit.
!
the unit is powered up until the isolator switch in the "OFF" position.
Y
Do not start the compressor for more than 10 times.
5.3 Screens displayed
5.3.1 Main Screen
Unit Status
OFF: Off
ON: On
OF RMT: Off by remote contact
OF CMP: Off by remote contact
Shows
Alarm code
Shows bypass (operating only with Winter /
Summer enabled)
Bypass close
Bypass open
English
5.3.2 USER PARAMETER
Press the key Prg and enter on MAIN MENU
Select USER SETTINGS, press Enter to confi rm.
Shows the "user setting menu":
Select DRYER SETTINGS press Enter to confi rm. This Screen appears
Temperature of
Dew point
or
Temperature
Inlet Absorber
(operating in sum-
mer)
With the keys Up,Down and Enter you can select/change a parameter:
U1 - SET of Dew Point
Level indicator
U2 -Work pressure [barg]
of Dewpoint
U3 - Working Mode: Forced Rig. O Normal
temperature
U4 - Alarm Relay Mode by: alarms&warnings or allarms.
U6 - DPM: Fitted o No Fitted with the control fo the dew point (Fitted)
or with fi xed time (No Fitted)
U15 - By-pass. mode (automatic/manual)
U17 - Pressure: mode (automatic/manual)
U18 - Pressure
U20 - Dew point: mode (automatic/manual)
When you change the parameter press Enter to confi rm.
Press Esc to return on USER SETTINGS MENU.
Select DATE for change the date and the time:
Date / hour
This Screen appears:
- - -Main Menu - - -
START/STOP
USER SETTINGS
SERVICE
INFORMATION
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
U1 - DEWP.SET (°C):
-40
U2 - PRESSURE (barg):
07
U3 - MODE: Forced Rig.
U4 - ALARM RELAY MODE:
by: ALARMS & WARNINGS
U6 - DPM:
NO FITTED
AUTOMATIC PRESSURE
U17 - MODE:
MANUAL
U18 - READ P.:
00 bar
AUTOMATIC BY-PASS
U15 - BY-PASS MODE:
MANUAL
DEW POINT AUTOMATIC
U20 - MODE:
MANUAL
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
2011/Oct/24
15.49
Change: NO
M10
ATT060-090
Press esc to return on USER SETTINGS MENU.
Select BMS:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
- BMS -
U7 - ADRESS:
U8 - BAUDRATE:
The parameters U7 and U8 selects the adress fo the supervision.
Press esc to return on the USER SETTINGS MENU.
Select MOISTURE DRAIN:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
- MOISTURE DRAIN -
U9 - MODE: Continue
U10 - TIMED
On (s):
U11 - TIMED
Off (s):
U9 - Mode condensate drain (continue; timed; capacitive);
U10 - Time "ON" with timed condensate drain;
U11 - Time "OFF" with timed condensate drain;
Press Esc to return on USER SETTINGS MENU.
Select OTHER:
- User Settings Menu -
DRYER SETTINGS
DATE/TIME
BMS
MOISTURE DRAIN
OTHER
LANGUAGE
This Screen appears:
U12 - BACKLIGHT ON:
U13 - Enable Money
:
U14 - Money : Euro
U15 - Money / KWh
:
0.120
U16 - Saving Compared
to Heatless
5.3.3 SERVICE PARAMETER
On MAIN MENU select Service and press Enter to confi rm.
001
9600
1
NO
NO
U2
5 / 14

Publicité

loading

Ce manuel est également adapté pour:

Antares att090