7
Hälytys -/varoitusluettelo
Hälytys
Näyttö
Koodi
A01
WARNING PROBE AD InletTemperature
WARNING PROBE Purge Air Tempe-
A02
rature
A03
WARNING PROBE Dewpoint Meter
WARNING PROBE Heater Outlet Tem-
A04
perature 1
WARNING PROBE Heater Outlet Tem-
A05
perature 2
WARNING PROBE Compressor Di-
A06
schargeTemperature
WARNING PROBE Thermal MassTem-
A07
perature
A08
WARNING PROBE Capacitive Level
ALARM FRIDGE High Pressure by
A09
pressure switch
ALARM FRIDGE High Temperature by
A10
temperature switch
WARNING ADSORBER High AD Inlet
A11
Temperature
ALARM FRIDGE Low AD Inlet Tempe-
A12
rature
WARNING ADSORBER High Electrical
A13
Heater Temperature Column 1
WARNING ADSORBER High Electrical
A14
Heater Temperature Column 2
WARNING ADSORBER Low Electrical
A15
Heater Temperature Column 1
Suomi
ATT
ATT
ATT
Nollaus
025-040
060-090
140-340
A
X
X
A
X
X
X
A
X
X
X
A
X
x
X
A
X
X
X
A
Nu
X
A
Nu
X
A
NU
X
A
X
X
A
X
Nu
A,
X
X
jos T < 13
°C(**)
A
X
X
A,
X
X
X
jos T < 150
°C (**)
X
X
X
X
A, T > (vastuk-
X
X
X
sen asetusarvo
– 30 + 20) (**)
Viive
Oletusarvoiset hälytysolosuhteet
AIN Ad tulolämpötila
4 s
AIN tyhjennysilman lämpötila
3 s
AIN kastepistemittari
3 s
AIN lämmittimen ulostulolämpötila A ANTURI ei kytketty tai
3 s
AIN lämmittimen ulostulolämpötila B ANTURI ei kytketty tai
3 s
AIN kompressorin tyhjennyslämpötila
3 s
AIN lämpömassan lämpötila ANTURI ei kytketty tai viallinen
3 s
AIN kapasitiivinen taso
3 s
DIN Kylmäaineen korkean paineen painekytkin
Välitön
DIN Korkean lämpötilan kytkin
Välitön
180 s
180 s
5 s
A, jos T <
150 °C (**)
600 s
ATT060-090
Kompressori
seis
K
E
E
E
viallinen
E
viallinen
K
E
E
K
K
E
K
E
5 s
E
E
Kuivain
Hälytysrele
seis
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
E
Aktiivinen
9 / 14