7
Lista allarmi
Codice
Display
Allarme
WARNING PROBE AD Inlet-
A01
Temperature
WARNING PROBE Purge Air
A02
Temperature
WARNING PROBE Dewpoint
A03
Meter
WARNING PROBE Heater
A04
Outlet Temperature 1
WARNING PROBE Heater
A05
Outlet Temperature 2
WARNING PROBE Compres-
A06
sor DischargeTemperature
WARNING PROBE Thermal
A07
MassTemperature
WARNING PROBE Capacitive
A08
Level
ALARM FRIDGE High Pressu-
A09
re by pressure switch
ALARM FRIDGE High Tempe-
A10
rature by temperature switch
WARNING ADSORBER High
A11
AD Inlet Temperature
ALARM FRIDGE Low AD Inlet
A12
Temperature
WARNING ADSORBER High
A13
Electrical Heater Temperature
Column 1
WARNING ADSORBER High
A14
Electrical Heater Temperature
Column 2
WARNING ADSORBER Low
A15
Electrical Heater Temperature
Column 1
Italiano
ATT
ATT
ATT
Reset
025-040
060-090
140-340
X
X
A
X
X
X
A
X
X
X
A
X
X
X
A
X
X
X
A
NU
X
A
NU
X
A
NU
X
A
X
X
A
X
Nu
A
A,
X
X
se T<13°C(**)
X
X
A
A,
X
X
X
se T<150°C(**)
X
X
X
X
A, T>(setpoint
X
X
X
resistenza – 30
+ 20) (**)
Ritardo
Condizioni di default per attivare l'allarme
4 s
AIN alta temperatura ingresso AD
3 s
AIN alta temperatura di purga
3 s
AIN sonda Dewpoint non funziona
3 s
AIN sonda temperatura uscita resistenza 1 non funzionante
3 s
AIN sonda temperatura uscita resistenza 2 non funzionante
3 s
AIN sonda sullo scarico compressore non funzionate
3 s
AIN sonda temperatura massa termica non funionante
3 s
AIN sensore di livello capacitivo non funzionante
Immediato
DIN alta pressione refrigrante
Imm.
DIN alta Temperatura refrigerante
180s
180s
5s
A, se
T<150°C
(**)
600s
ATT060-090
Stop
Compressore
5s
Stop
Alarme
Dryer
relay
S
N
Attivo
N
N
Attivo
N
N
Attivo
N
N
Attivo
N
N
Attivo
S
N
Attivo
N
N
Attivo
N
N
Attivo
S
N
Attivo
S
N
Attivo
N
N
Attivo
S
N
Attivo
N
N
Attivo
N
N
Attivo
N
N
Attivo
9 / 14