Possibilities of professional cable
extension on site (IP 68)
The SonicControl cable is 10 metres long.
On site, this cable can be extended by a
qualified electrician up to max. 60 metres
without any change in cross-section being
necessary.
SonicControl probe extension to max. 60
metres 0,75 mm
2
Note:
The regulations set out by the directive
VDE 0100 must be heeded. The switch unit
must not be installed in potentially explosi-
ve areas. The 10 m cable can be extended
on site to up to 60 m. If the cable is routed
in a cable channel with cables from other
frequency-controlled units, a shielded cable
has to be used
395-016
Electrical connection
Fig.1
Fig.2
Fig.3
Fig.4
49
Fig. 1:
Crimp cable extension with butt joint
Fig. 2: Shell is placed around the cable,
both shell ends are sealed
Fig. 3: Cast the shell with prepared cas-
ting resin
Fig. 4: Final state with sealing plug
Individual parts on request