Salicru SLC TWIN RT3 Mode D'emploi page 70

Masquer les pouces Voir aussi pour SLC TWIN RT3:

Publicité

Les langues disponibles

Les langues disponibles

Problem shown on
the LCD display
Charger max. volt.
Charger min. volt.
Battery fault
UPS temp. fault
Min. inverter (V)
Max. inverter (V)
Output short circuit
Inverter overload
Calibration fault
Tab. 17. List of problems and solutions.
If the UPS does not work correctly, check the information displayed
on the LCD screen of the control panel and act accordingly
depending on the unit model.
Using the help guide in Tab. 17, try to solve the problem and if it
persists, contact our Technical Service and Support T.S.S..
When it is necessary to contact our Technical Service and Support
T.S.S., provide the following information:
UPS model and serial number.
Date the problem occurred.
Complete description of the problem, including the informa-
tion provided by the LCD display or LEDs and alarm status.
Power supply condition, load type and load level applied to the
UPS, ambient temperature, ventilation conditions.
Battery information (capacity and number of batteries).
Other information that you deem relevant.
9.4. WARRANTY CONDITIONS.
9.4.1. Warranty terms.
On the SALICRU, S.A. website you will find the warranty condi-
tions for the product you have purchased and you can register it
there. It is recommended to do this as soon as possible in order to
include it in our Technical Service and Support's
Among other advantages, it will be much more efficient to carry
out any regulatory procedure for intervention of the
event of a hypothetical fault.
70
Possible cause
The battery charge voltage is too high
The battery charge voltage is too low
The battery needs to be replaced or is faulty
The internal temperature of the UPS is high (due to dllo,
the UPS has switched to Bypass or has stopped)
The inverter voltage is too low
The inverter voltage is too high
Short circuit in the output
Overload in the inverter.
Max. (P,S) > L2 (L2 = 105%) max. counter reached
Calibration failed
(T.S.S.)
Consult the Distributor
Consult the Distributor
Consult the Distributor
Check the ventilation of the UPS and the ambient temperature
Consult the Distributor
Consult the Distributor
Disconnect all loads. Turn off the UPS
Check whether the output and loads of the UPS are short-circuited
Make sure to eliminate the short circuit before starting it up again
Check the loads and disconnect any that are non-critical
Consult the Distributor
9.4.2. Exclusions.
SALICRU, S.A.
the defect in the product does not exist or was caused by improper
use, negligence, improper installation and/or verification, attempts
at unauthorised repair or modification, or any other cause beyond
the intended use, or by accident, fire, lightning or other hazards.
Nor shall it cover any compensation for damages.
9.5. TECHNICAL SERVICES NETWORK.
Information about our national and international Technical Service
and Support
database.
T.S.S.
in the
Solution
will not be bound by the warranty if it notices that
(T.S.S.)
centres can be found on our website.
Code (shown
in the event
log)
502
503
607
706
70C
70D
805
808
815