7.4. DESCRIPTION OF THE LCD DISPLAY.
The LCD backlight automatically dims after 10 minutes of inactivity.
Press any button to restore the screen, except the on/off button.
Fig. 33. SALICRU logo.
The logo graphic above is the default screen during logical
power-up and is displayed for the first 5 seconds. After this time,
the status screen or the first start menu appears if the unit is being
started up for the first time.
The control buttons have no effect during these first 5 s.
7.5. MAIN SCREEN.
Status screen 1
Status screen 3
Fig. 34. Status screens.
Once the UPS has been started up, the system will enter this
main screen by default. Each screen is automatically displayed for
3 seconds.
Press
to block and
display.
62
Status screen 2
to automatically restore the
Operating
status
Battery
status
Fig. 35. Description of the LCD display.
The following table describes the UPS status information.
Operating status
Cause
Standby mode
On-Line mode
1 beep every
4 sec.: Battery
mode
1 beep every
sec.: Battery
mode with
low batt.
HE (high
efficiency)
Frequency
converter
(CVCF)
Bypass mode
Battery test
Battery fault
IoT
status
Load/unit
status
Description
The UPS is off and without output.
The UPS is operating normally and
protecting the loads.
A mains failure has occurred and
the UPS is supplying the loads via
the battery. Prepare the loads for
shutdown.
This warning is approximate and
the actual shutdown time may vary
significantly.
Indicates that the device is supplying
voltage via the Bypass (ECO mode).
1. The function can be enabled via the
LCD screen settings or the software
(Winpower, etc.).
2. Please note that the transfer time
of the UPS in high efficiency (HE)
mode to Battery mode is about 10 ms,
which may be too long time for certain
critical loads.
The UPS would work with a fixed
output frequency (50 Hz or 60 Hz).
The maximum output power and
maximum load current must be reduced
to 60% in Frequency converter mode.
The function can be enabled via the
LCD screen settings or the software
(Winpower, etc.).
An overload or fault has occurred,
or a command has been received,
and the UPS is in Bypass mode.
The UPS is running a battery test.
The UPS detects that the battery is
faulty or disconnected.