7.2. LCD DISPLAY FUNCTIONS.
When starting the UPS, the display shows the summary screen of
the default status of the UPS.
Main
Submenu
menu
UPS status
Event log
Measure-
ments
Switch to
Bypass
Load segment
Start battery test Start manual battery test
Start WLAN
configuration
Finish WLAN
Control
configuration
Reset fault
status
Reset event list
Reset
integrated IoT
Restore factory
settings
Settings
Identifica-
tion
Tab. 13. Default UPS statuses.
7.3. USER SETTINGS.
Submenu
Password
It can be changed by the user.
Change
English, Italian, French, German, Spanish,
language
Polish, Catalan, Portuguese
User password
[Enabled, ****], [Disabled]
Audible alarms
[Enabled], [Disabled]
Output voltage
[200 V], [208 V], [220 V], [230 V], [240 V]
USER MANUAL
Display information or menu function
UPS mode, IoT status, date/time,
battery status and current alarms.
Shows stored events and faults
[Load] W VA AP%, [Input/Output] V Hz,
[Battery] % min V EBM, [DC Bus] V,
[Temperature] C
Transfer of the UPS to Bypass Mode
Load segment on/off
If the WLAN status is in configuration mode,
the available option will be "Finish WLAN
configuration", otherwise the available
option will be "Start WLAN configuration"
Clear active fault.
Clear events and faults.
Reset the IoT and modbus TCP function in
the UPS.
Reset to factory default settings
See user settings
[Product type], [Model], [Serial number],
[UPS firmware], [Embed IoT firmware],
[Embed Ethernet IP], [WLAN IP],
[Embed Ethernet MAC], [WLAN MAC]
Default
Available settings
settings
0000
English
[Enabled]
[Enabled]
[230 V]
Submenu
Available settings
Output
[Normal auto detect], [50 Hz, 60 Hz
frequency
converter]
High efficiency
[Enabled], [Disabled]
mode
Auto Bypass
[Enabled], [Disabled]
Cold start: [Disabled], [Enabled]
Default settings: Enabled = the unit can
be started via the batteries (only in the
absence of mains power).
Other options: Disabled = battery start
not allowed.
Auto restart: [Disabled], [Enabled]
Default settings: Enabled = the UPS will
restart in Normal mode after network
Cold start/Auto
recovery if the UPS stopped due to the
restart/Start on
battery voltage dropping below the
bypass
cut-out level.
Other options: Disabled.
Start in Bypass: [Disabled], [Enabled]
Default settings: Disabled = the UPS will
start in On-Line mode.
Other options: Disabled = the UPS will
start in Bypass mode, it will remain in
Bypass mode for 5 s, and will switch to
On-Line mode.
Wiring fault
[Enabled], [Disabled]
Overload
[50%÷105%]
pre-alarm
[Auto Detection], [Manual EBM: 0÷4],
External battery
[Manual Ah: 7÷144 Ah] [No battery]
[2 A], [4 A], [6 A], [8 A] for long autonomy
Charger current
model.
[Disabled], [Remote activated],
Dry in signal
[Remote deactivated], [Forced bypass],
[Remote MBP]
(2)
[load powered], [on batt.], [batt. low],
Dry out signal
[batt. open], [bypass], [UPS ok]
Ambient temp.
[Enabled], [Disabled]
alarm
Remaining
[Enabled], [Disabled]
battery time
Date and time
dd/mm/yyyy hh:mm
Time zone
Set time zone
LCD contrast
[0-100%]
Modbus TCP
[Enabled], [Disabled]
Enable
[Yes], [No]
internal IoT
The "No battery" function is available with FW version 00.01.13478 or later.
(1)
The "Remote MBP" function is available with FW version 00.01.13478 or later
(2)
Tab. 14. User settings.
SLC TWIN RT3 0.7÷3 kVA UNINTERRUPTIBLE POWER SUPPLY (UPS)
Default
settings
Normal
automatic
detection
50 Hz/60 Hz
[Disabled]
[Enabled]
Cold start:
enabled
Automatic
restart:
enabled
Start in Bypass:
disabled
[Disabled]
105%
Auto detection
0 EBM
(1)
4 A
[Remote MBP]
[on batt.]
[Enabled]
[Enabled]
01/01/2022 00:00
GMT+1
50%
[Disabled]
[Yes]
61