9. MAINTENANCE, WARRANTY
AND SERVICE.
9.1. UNIT MAINTENANCE.
SLC TWIN RT3
The
For best preventative maintenance, keep the area around the unit
clean and free of dust. If the environment is very dusty, clean the
exterior of the system with a vacuum cleaner.
9.2. BATTERY MAINTENANCE.
Pay attention to all of the safety instructions regarding the
batteries, indicated in the EK266*08 manual, section 1.2.3.
The service life of the batteries depends significantly on the
ambient temperature and other factors such as the number of
charges and discharges, as well as the depth of these.
Their design lifetime is between 3 and 5 years if the ambient tem-
perature to which they are subjected is between 10 and 20ºC.
On request, batteries of a different type and/or design lifetime can
be supplied.
The batteries used in standard models are sealed lead-acid,
valve-regulated and maintenance-free. The only requirement is to
charge the batteries regularly to extend their life expectancy.
As long as the UPS is connected to the supply network, whether
or not it is in operation, it will keep the batteries charged and will
also provide protection against overcharging and deep battery
discharge.
9.2.1. Replacing the batteries.
If a connection cable must be replaced, purchase original materials
through our T.S.S. or authorised distributors. Using inappropriate
cables can lead to overheating in connections that are a fire risk.
There are permanent dangerous voltages inside the unit,
even without mains supply present, due to its connection
with the batteries, and especially in UPS units where the electronics
and batteries share the same box.
Also take into consideration that the battery circuit is not isolated
from the input voltage, so there is a risk of discharge with dangerous
voltages between the battery terminals and the earth terminal,
which in turn is connected to the earth (any metal part of the unit).
DO NOT DISCONNECT
Battery mode.
Repair and/or maintenance work is reserved for the T.S.S.,
except for battery replacement, which can also be
carried out by qualified personnel who are familiar with them.
No other person should handle them.
68
series requires a minimal maintenance.
the batteries when the UPS is in
Internal battery replacement procedure.
Press the button on both sides of the front panel with force in
1.
order to remove it.
Fig. 42. Removing the front panel.
Disconnect the battery connector.
2.
Unscrew the screws on the battery support.
3.
Remove the battery support.
4.
Remove the batteries.
5.
Fig. 43. Steps for removing the internal battery.
Install the new battery pack in the UPS.
6.
Screw the metal protective caps and the front panel back on.
7.
Check the new batteries.
8.
Check that the replacement batteries have the same rating
and are the same brand as the replaced batteries.
SALICRU