MB TWIN RT3 0/2x3AB147 40 A EE521925
B
D
Tab. 1. Input/Output connector types.
Note related to batteries, code B1:
(B1) Device with a more powerful charger, which does
not have a battery pack, nor the possibility of
installing them in the same box.
If the battery module is required, it will need to be
ordered as a separate item, which will be connected
to the UPS using the supplied cable.
Before connecting a module or group of batteries to
the unit or another available module,
to check
that the voltage value printed on the back of
the device next to the battery connector is appropriate
and that the polarity between the means of connection
corresponds.
For more information, see Chapter 10 of this document.
4.3. OPERATING PRINCIPLE.
This manual describes the installation and operation of Uninter-
ruptible Power Supplies (UPS) from the
with a power of ≤3 kVA.
optimum protection of any critical load, maintaining the supply
voltage of the loads between the specified parameters without
interruption during failure, deterioration or fluctuation of mains
power, and come in a wide range of models (from 0.7 kVA to 3 kVA),
enabling the end user to select the model that best suits his needs.
Thanks to their PWM (pulse width modulation) and double-con-
version technology,
cool, silent and high performance.
USER MANUAL
230 V
Input
Output
Schuko
IEC
UK
IEC
it is necessary
SLC TWIN RT3
SLC TWIN RT3
series UPS ensure
SLC TWIN RT3
series UPS are compact,
EE special battery module.
Protection rating.
Last three digits of the battery code.
Letters of the SALICRU battery family code.
Number of batteries of a single branch.
Number of battery branches in parallel.
Empty battery module. Includes accessories for battery connection.
TWIN RT3 battery module series.
RACK Battery rack.
MB
Battery cabinet/box.
The double converter principle eliminates all mains power distur-
bances. A rectifier converts the AC current of the mains into DC
current, thereby maintaining optimum battery charge level and
powering the inverter, which, in turn, generates a suitable AC sine-
wave voltage for continuously powering the loads. In the event of
failure of the UPS's mains power, the batteries supply clean power
to the inverter.
The design and construction of the
has been carried out in accordance with international standards.
This series has therefore been designed to maximise the avail-
ability of critical loads and ensure that your business is protected
against variations in voltage, frequency, electrical noise, interrup-
tions and micro-interruptions, present in power distribution lines.
This is the primary goal of
This manual is applicable to standardised models and those
indicated in Tab. 2.
4.4. BLOCK DIAGRAM.
Input
filter
series
Charger
Fig. 7. UPS block diagram.
SLC TWIN RT3
series UPS
SLC TWIN RT3
series UPS.
DC/AC
Output
inverter
filter
Battery
SLC TWIN RT3 0.7÷3 kVA UNINTERRUPTIBLE POWER SUPPLY (UPS)
47