PROBLEM
ALARM SIGNAL
The barrier does
not open or close.
POSSIBLE CAUSE
Release device open.
Open barrier inspection hatch
(if the emergency stop micro-
switch is installed).
LOCKS connectors incorrectly
connected.
STOP button/contact active for
more than 5 s.
For MASTER-SLAVE systems,
the ACS/BA/60 BreakAway sy-
stem is active on the MASTER
barrier.
Encoder 1 not connected.
Encoder 2 not connected.
Severe encoder 1 malfunction.
Severe encoder 2 malfunction.
(EnE5)
Encoder 1 malfunction.
Operation in battery mode.
Encoder 2 malfunction.
Operation in battery mode.
Encoder 1 calculation error.
Encoder 2 calculation error.
Inverter overheat protection
triggered.
(btLO)
Flat batteries.
No RS485 serial communica-
tion between MASTER barrier
and SLAVE barrier.
Serial communication interfer-
detected.
fer error between MASTER and
SLAVE.
Controller unit models not com-
patible.
(COM5)
ware versions of controller
units.
CORRECTIVE ACTION
AGILIK-KB-BI/004HP-BI/006-BI/008
ing the key two complete turns clockwise.
BIONIK4
key.
Close the inspection hatch correctly and check the
micro-switch connection.
Check the connector connections.
Jumper one of the two LOCKS connectors.
Check connections to STOP button.
Check the BreakAway system and if the alarm event
is solved, re-engage the ACS/BA/60 system.
Check connection to encoder.
Replacing the encoder is recommended if the prob-
lem persists.
Check connection to encoder.
Replacing the encoder is recommended if the prob-
lem persists.
Press TEST button. If the error code is displayed
again, switch off the controller unit, wait 5 seconds
and switch on again. Replace the encoder if the prob-
lem persists.
Press TEST button. If the error code is displayed
again, switch off the controller unit, wait 5 seconds
and switch on again. Replace the encoder if the prob-
lem persists.
Press TEST button or perform 3 command requests
in succession. Replace the encoder if the problem
persists.
Press TEST button or perform 3 command requests
in succession. Replace the encoder if the problem
persists.
Repeat acquisition procedure.
Repeat acquisition procedure.
Function is restored automatically within 2 minutes.
Wait for mains power to be restored.
Check connection to terminals COM-LNA-LNB.
Check settings of parameter
Check that battery kit is installed on both MASTER
and SLAVE barriers.
Check settings of parameter
-
Check connection to terminals COM-LNA-LNB.
Check installation and replace one or both control-
ler units.
-
Check parameter
. Both controllers must have the
Contact the technical assistance.
-
.
.
93