Directional mode 2.
When entering, the barrier is opened with an AP open command, and closes after the automatic closing
time set with parameter
NOTE
When leaving the parking area, the barrier is opened by a PED command received from the magnetic loop.
Once the vehicle has crossed the barrier and released contact FT (NC), the barrier closes.
NOTE
Enable close command after activation of photocell (FT)
N.B.
Disabled.
Enabled. The barrier stops if the photocell is activated during closing manoeuvre. The barrier resumes
closing when the photocell is cleared.
Selection of the battery operation management
Setting a value different than
be selected via parameter
The control unit always accepts commands until the battery is completely exhausted.
The command becomes active when the battery voltage drops to the minimum threshold (22Vdc for
battery 2x12Vdc)
The command becomes active when the battery voltage drops to the medium threshold (23Vdc for
battery 2x12Vdc)
The command becomes active when the battery voltage drops to the maximum threshold (24Vdc for
battery 2x12Vdc)
Selecting the battery operation limitations
N.B.: the parameter is visible only if par.
There is no limitation for the commands when the battery voltage drops under the selected threshold. An
error alert may be activated via the SC output (if parameters
When the battery voltage drops under the threshold selected with par.
opening commands and does not perform closing.
When the battery voltage drops under the threshold selected with par.
control unit automatically opens the barrier's boom and accepts only a closing command.
It accepts only closing commands even if the ORO input is active and if the parameter is
When the battery voltage drops to the threshold selected with par.
of 5s, automatically closes the gate and accepts only one opening command.
Selection of the battery type and consumption reduction
NOTE
the display shows the message
.
Battery 24Vdc (2x12V) with B71/BCHP. Acceleration/deceleration/speed reduction enabled, to increase
the battery life.
Battery 24Vdc (2x12V) with B71/BCHP. No performance reduction, maximum battery consumption.
Battery 36Vdc (3x12V) with external charger. Acceleration/deceleration/speed reduction enabled, to
increase the battery life. - DO NOT SELECT. FUTURE USE -
Battery 36Vdc (3x12V) with external charger. No performance reduction, maximum battery consumption.
- DO NOT SELECT. FUTURE USE -
Restoring factory default values
NOTE This procedure is only possible is NO data protection password is set.
N.B.: This parameter is not visible for the SLAVE barrier.
• Press and hold the
• The display flashes after 4 s
• The default factory settings have now been restored.
88
.
.
a battery voltage level check is activated. The desired operation type can
and an error alert can be activated through the SC output via parameter
(if set to
P1
P2
x4 s
(up arrow) and
.
different to
is different than
and
or
and the battery is 2x12Vdc) or an error alert
Warning! Restoring default settings cancels all settings
made previously except for parameter
check that all parameters are suitable for the installation.
The default factory settings may also be restored using
the
(up arrow) and
Turn off the power.
(down arrow) button until the unit switches on.
.
.
are adequately set).
, the control unit accepts only
, after a 5 s pre-flashing, the
.
the control unit, after a prelamping
.