Normally not powered. The electric lock is powered for 1,5 s at the start of the opening manoeuvre to
allow the barrier to open.
Magnetic "ventouse" electric lock normally powered when the barrier is completely closed. Not powered
when the barrier is moving or completely open
Magnetic "ventouse" type electroblock with demagnetizer B72/DGS
NOTE: In the case of MASTER/SLAVE installation, in order to use the selection par.
Obstacle detection function setting (crush prevention)
The barrier reopens if the obstacle detection system is activated during a closing manoeuvre.
During opening manoeuvres, the barrier is reversed by the obstacle detection system only if the obstacle
The maximum number of automatic closing attempts is set by parameter
N.B.: Available values may be limited by the setting for parameter
= minimum activation time (maximum sensitivity)...
The barrier remains stationary against the obstacle for a maximum time of 5 s before reversing.
Setting opening start acceleration
Setting closure start acceleration
= the barrier accelerates rapidly at start of manoeuvre ...
gressively at start of manoeuvre.
N.B.: Available values may be limited by the setting for parameter
Setting opening speed (%)
Setting closure speed (%)
= 10% minimum speed ...
N.B.: Available values may be limited by the setting for parameter
Approach speed setting
This parameter sets the motor speed when approaching the barrier open/closed stop.
= 10 motor revolutions per minute (RPM) ...
Opening approach distance setting
Closing approach distance setting
from 0,5 to 3 of turns performed by the motor at speed set with parameter
N.B.: Available values may be limited by the setting for parameter
Number of automatic closure attempts after activation of sensing edge or ob-
stacle detection (crush protection)
No automatic closure attempts.
From 1 to 3 automatic closure attempts.
Automatic closure is only performed if the barrier is completely open.
Set a value equal to or lower than the value set for parameter
Photocell mode for barrier opening (FT)
N.B.: this parameter is not visible if the value of parameter
DISABLED. Photocell is not active or not installed.
STOP. The barrier stops and remains stationary until the next command is received.
IMMEDIATE REVERSE. The barrier reverses immediately if the photocell is activated during opening manoeuvre.
TEMPORARY STOP. The barrier stops and remains stationary as long as the photocell is obstructed. The
barrier resumes opening when the photocell is cleared.
DELAYED REVERSE. The barrier stops if the photocell is obstructed. The barrier closes when the photocell
is cleared.
Photocell mode for barrier closure (FT)
N.B.: this parameter is not visible if the value of parameter
DISABLED. Photocell is not active or not installed.
STOP. The barrier stops and remains stationary until the next command is received.
= maximum activation time (minimum sensitivity).
= 100% maximum speed.
= 100 motor revolutions per minute (RPM).
=
.
.
= the barrier accelerates slowly and pro-
.
.
.
.
.
=
,
or
.
=
,
or
.
it is necessary
85