Installation
Outputs
Installer mode -> Test -> Outputs
Here you can see the number, name, output type and current status (off or on) of the output.
You can also switch the output for test purposes here.
Loudspeaker
Installer mode > Test > Int. sounders
Alarm panel:
Installer mode > Test > Sounders & signallers -> Int. sounders
This test also activates the hybrid module loudspeaker with a "test tone".
It sends a "test tone" to all available internal sounders (indoor signaller, info module,
control panel). All these components are activated at the same time.
Note
You can set the volume of the different signal tones on the loudspeaker in the user
menu.
Note
User menu -> Configuration -> Volume settings ->
Operator Sounds
Info tones:
Alarm tones:
The test menu point
Installer mode -> Test -> Loudspeaker
Note
Alarm panel:
Installer mode > Test > Sounders & signallers -> Loudspeaker
is used for the speech playback of the alarm panel's voice messages.
MAINS FAIL, LOW BATT and TR
• Open and close the connected circuits.
• Check if the correct notifications are shown on the alarm panel.