Wiring Options; Wiring The Rigmaster™ Emergency Battery Back-Up Led Luminaire - Emerson Appleton Rigmaster Feuille D'instructions

Luminaire à led avec batterie de secours
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Wiring Options

WARNING: The luminaire must be grounded as required by the National Electrical Code (Paragraph 410.21 and Article 250) or
Canadian Electrical Code (Rule 30-500 and Section 10). Verify that ground continuity has been established by using an Ohm meter or
other suitable testing equipment before energizing the luminaire. Failure to properly ground the luminaire will create an electric shock
hazard, which can cause serious injury or death.
Please use supply wires with temperature rating 90°C or above.
Wiring the Rigmaster™ Emergency Battery Back-up LED Luminaire
For Luminaire with Wire Nut Option
NOTE: Each wire nut can accept 2 # AWG12 (user wires) with 1 # AWG18 wires (Driver wire). Refer to the table below for
power system application.
POWER SySTEM
L-N AC POWER SYSTEM
L-L AC POWER SYSTEM
1.
Make sure power is Switched off before wiring the luminaire.
2.
A.
Wiring with Multi-conductor Cable: Strip the cable outer jacket as required. Strip the insulation of individual wire by
approximately 13 mm (0.5 in)
B.
Wiring with Individual Wires: Strip the insulation of individual wire by approximately 13 mm (0.5 in)
3.
For standard Wiring:
A.
Open the luminaire wiring compartment by loosening the eight captive screws. Allow the cover to swing open, enabling
access to the wiring compartment. See Figure 5. Pull in the luminaire's supply input wires (by removing wire nuts) through
the cable entry hole, inside the wiring compartment.
B.
Pull in the facility electrical supply wires through the same conduit entry hole.
C.
Connect electrical power supply leads to wire conductors with the help of wire nuts by holding wires together with even
ends. For Wiring diagram refer to one of the figures from Figure 7A, Figure 7B, Figure 7C, & Figure 7D in conjunction
with section 'Wiring Methods' as applicable.
D.
Connect the battery by plugging in the quick connector.
E.
Check all connections for continuity and ground integrity and close the luminaire wiring compartment cover.
F.
Tighten the eight captive screws by applying a torque of 2.25 N.m (20 lbf-in) using the sequence shown as in figure 11.
Make sure wires do not pinch between cover and wiring compartment while closing.
4.
For through feed Wiring (for all conduit sizes):
A.
Open the luminaire wiring compartment by loosening the eight captive screws on cover. Allow the cover to swing
open, enabling access to the wiring compartment. See Figure 5.
B.
Pull in the luminaire's supply input wires (by removing wire nuts) through the cable entry hole, inside the
wiring compartment.
C.
Pull in the facility electrical supply wires from both sides through the conduit entry holes.
D.
Connect electrical power supply leads to the respective wires with the help of wire nuts supplied with luminaire by holding
wires together with even ends. For Wiring diagram refer one of the figures from Figure 8A, Figure 8B, Figure 8C, & Figure
8D in conjunction with section 'Wiring Methods' as applicable.
E.
Connect the battery by plugging in the quick connector.
F
Check all connections for continuity and ground integrity and close the luminaire wiring compartment cover.
G.
Tighten the eight captive screws by applying a torque of 2.25 N.m (20 Lb.in) using the sequence shown as in Figure 11.
Make sure wires do not pinch between cover and wiring compartment when closing.
5.
Apply TLNC4 grease on plugs (3 supplied) in 3 lines, spaced approximately 120 degrees apart, perpendicular to the threads.
After applying TLNC4 grease close all unused conduit entries with plugs. Apply torque of 45 N.m (400 Lb.in.) for 3/4" NPT plug,
28 N.m (250 Lb.in.) for 1/2 " NPT plug and 25 N.m (225 Lb. in.) for M20 plug.
6.
For continuous row mounting below mentioned number of luminaires can be connected.
• Maximum 28 luminaires of 4300 lm connected in series
• Maximum 15 luminaires of 7600 lm connected in series
Appleton • 1.800.621.1506 • www.appletonelec.com
TABLE 3:
BLACk
HOT / LINE
HOT 1 / LINE 1
WHITE
NEUTRAL
HOT 2 / LINE 2
650610-000 Rev. 03 11/02/20 • Page 6 of 43
GREEN
GROUND
GROUND

Publicité

Table des Matières
loading