Tighten the eight captive screws by applying a torque of 2.25 N.m (20 Lb.in) using the sequence shown as in Figure 11. Make
sure wires do not pinch between cover and wiring compartment while closing.
9.
Apply TLNC4 grease on plugs (3 supplied) in 3 lines, spaced approximately 120 degrees apart, perpendicular to the threads.
After applying TLNC4 grease close all unused conduit entries with plugs. Apply torque of 45 N.m (400 Lb.in.) for 3/4" NPT plug,
28 N.m (250 Lb.in.) for 1/2 " NPT plug and 25 N.m (225 Lb. in.) for M20 plug.
10.
For continuous row mounting below mentioned number of luminaires can be connected.
Maximum 28 luminaires of 4300 lm connected in series.
Maximum 15 luminaires of 7600 connected in series
11.
Apply AC power to the unit. LED indicator on the luminaire should begin to flash green. If it flashes red; please refer to the
Troubleshooting/Maintenance section.
12.
Battery will be fully charged within 24 hours (maximum). Emergency luminaire may or may not light at this time, depending on
the degree to which battery is charged.
FIGURE 6: RIGMASTER EMERGENCy LUMINAIRE WITH SCREW TERMINAL OPTION
Wiring Methods
Wiring Method for 4 Wire Connection
1. Connect Direct supply Line to L' terminal/wire nut. See Figure 7A/7B/8A/8B/9A/9B/10A/10B as applicable.
2. Connect Line coming through AN external Switch to L terminal/wire nut. See Figure 7A/7B/8A/8B/9A/9B/10A/10B as applicable.
3. Connect Neutral & Ground to N terminal/wire nut & E/G terminal/wire nut respectively.
4. Please note both Lines (L and L') are from same source and are split to enable fixture control via a secondary switch for routine
on/off functionality while still keeping battery charged for emergency purposes.
5. Please note that interchanging line connection will result in inappropriate operation and will trigger emergency once supply is
disconnected through switch and will drain battery.
6. It is recommended to connect luminaire using one of the depicted wiring schemes only to ensure proper operation of emergency
luminaire.
Wiring Method for 3 Wire Connection
1. For wire nut option Connect Line wires to L wire & L' wire into one wire nut (refer fig 7C/7D or fig 8C/8D)
2. For fixed terminal option short L Wire & L' wire with in fixture with a connector (refer fig 9C/9D or fig 10C/10D).
3. Connect Neutral & Ground to N terminal/wire nut & E/G terminal respectively.
4. Please note that in this wiring scheme luminaire should be powered continuously to keep battery charged, absence of power
supply will trigger Emergency mode.