Emerson Appleton Rigmaster Feuille D'instructions page 5

Luminaire à led avec batterie de secours
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LOW PROFILE FIXED BRACkET (RMHLPB)
1. Make sure power is disconnected & circuit is de-energized before installing the bracket.
2. Determine appropriate mounting distance between holes on the brackets for your application. Refer to Figure 4(C).
3. Secure RMHLPB bracket to structural support member with appropriate bolts (not supplied) that can handle the weight of luminaire
in accordance with local building code and all other code requirements.
4. Raise luminaire to mounted RMHLPB bracket and secure using M8 washer and bracket mounting screw (M8 X 18) supplied with
the bracket on both sides.
5. Use locking screw (M8 X 18) supplied with the bracket such that they are diagonally opposite to each other on either side. Refer to
Figure 4(C) for hole locations. Make sure bracket is locked to its position.
6. Tighten all the screws to secure the luminaire in place with a torque of 15 N.m (133 Lb.in).
MOUNTING BRACkET COMPATIBILITy CHART FOR RETROFIT INSTALLATIONS
Manufacturer
Crouse Hinds
Dialight
AZZ™ Rigalite
"X" Denotes compatible with respective Cross reference.
Appleton • 1.800.621.1506 • www.appletonelec.com
FIGURE 4: MOUNTING OPTIONS - RHMLPB BRACkET
Table 2: Bracket Compatibility with Retrofit Installations
Part Number
DP1057MTK
LTXW4
LTXW4LP
LSXW4
53050
Appleton Part Number
RMHLSB
Large Swivel Bracket
X
X
X
X
X
650610-000 Rev. 03 11/02/20 • Page 5 of 43
RMHLPB
Low Profile Bracket
X
X
X
X
X