Installation Instructions Appleton™ Rigmaster™ LED Luminaire
with Emergency Battery Backup
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Product Safety
Signal Words Defined
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous
situation which, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury. NOTICE is used to address practices not related to physical injury.
Safety Instructions for Luminaire
WARNING:
• Before installation, ensure that the unit complies with the hazardous area classification. Refer to luminaire nameplate, located on
exterior of housing body, for suitability in specific hazardous locations.
• Do not open or remove the luminaire with the circuit energized.
• Do not remove or replace fuse when luminaire is energized.
• Do not use luminaire on ungrounded systems. Failure to ground this luminaire can result in an electric shock, which may be fatal.
• Do not mount near gas or electric heaters.
• Use two safety cables for installations experiencing high vibrations.
• Do not open when explosive atmospheres are present.
• Supply wires are to be rated for minimum 90°C.
• To reduce the risk of ignition of hazardous atmosphere, disconnect the luminaire from the main supply circuit and wait until the
battery gets de-energized (Minimum 90 minutes for RM********H*** and minimum 180 minutes for RM********E***) before opening the
fixture. Keep tightly closed when in operation.
• Make sure to tighten unused close-up plugs after applying TLNC4 grease. TLNC4 grease shall be applied in 3 lines, spaced
approximately 120 degrees apart, perpendicular to the threads.
CAUTION:
• Do not look directly at the LEDs when energized.
• Disconnect the luminaire from the supply circuit before opening to reduce the risk of ignition in hazardous atmospheres.
• Disconnect battery pack through quick disconnect while opening luminaire for servicing.
• Do not attempt to service the battery. The unit uses a sealed, Ni-MH battery which requires no maintenance. For replacement,
contact Customer Service.
• To avoid burning hands, allow luminaire to cool down prior to maintenance.
• Do not replace any component in hazardous area. Move the luminaire into the area known to be non-hazardous.
• Lens cleaning instructions: Wipe/clean from the outside only with a moist cloth. (Beware of electrostatic charges.)
• When installing in a hazardous location, it is necessary that the reflector, lens, and all certified conduit plugs be in place and
tightened securely to the housing.
NOTICE:
• Do not touch the LEDs; touching could leave oily deposits, causing hot spots and potential premature failure.
• The LED lens should be cleaned periodically from the outside only with a moist cloth to maintain lighting efficiency.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• This luminaire is designed for and should be installed with hazardous locations wiring method required in accordance with the
National Electrical Code
®
• This product must be installed in accordance with the applicable installation code by a person familiar with the construction and
operation of the product and hazards involved.
• Do not use this equipment for anything other than its intended use.
• This luminaire is provided with a factory installed emergency lighting battery pack.
Appleton • 1.800.621.1506 • www.appletonelec.com
/Canadian Electrical Code and all applicable local codes.
650610-000 INSTRUCTION SHEET
650610-000 Rev. 03 11/02/20 • Page 1 of 43

Publicité

Table des Matières
loading

Sommaire des Matières pour Emerson Appleton Rigmaster

  • Page 1 650610-000 INSTRUCTION SHEET Installation Instructions Appleton™ Rigmaster™ LED Luminaire with Emergency Battery Backup FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS. Product Safety Signal Words Defined DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
  • Page 2 Applications/Intended Use • Areas where flammable gases and vapors are present under conditions defined by the ratings below. • Areas of low clearance, low ceiling heights, or where luminaire weights must be minimized. • Non-hazardous locations where severe weather conditions, excessive moisture, dirt, dust, corrosive atmospheres, and high ambient temperatures are encountered.
  • Page 3 Dimensions/Details LUMINAIRE DIMENSIONS FIGURE 1: RIGMASTER 2 FT. LUMINAIRE WITH EMERGENCy BATTERy BACkUP FIGURE 2: RIGMASTER 4 FT. LUMINAIRE WITH EMERGENCy BATTERy BACkUP General Mounting Instructions 1. Make sure power is disconnected before installing the luminaire. 2. Determine appropriate mounting distance between mounting holes for your application. 3.
  • Page 4: Mounting Brackets

    Mounting Brackets LARGE SWIVEL BRACkET (RMHLSB) 1. Make sure power is disconnected & circuit is de-energized before installing the bracket. 2. Determine appropriate mounting distance between holes on the brackets for your application. Refer to Figure 3(C). 3. Secure RMHLSB bracket to structural support member with appropriate bolts (not supplied) that can handle the weight of luminaire in accordance with local building code and all other code requirements.
  • Page 5 LOW PROFILE FIXED BRACkET (RMHLPB) 1. Make sure power is disconnected & circuit is de-energized before installing the bracket. 2. Determine appropriate mounting distance between holes on the brackets for your application. Refer to Figure 4(C). 3. Secure RMHLPB bracket to structural support member with appropriate bolts (not supplied) that can handle the weight of luminaire in accordance with local building code and all other code requirements.
  • Page 6: Wiring Options

    Wiring Options WARNING: The luminaire must be grounded as required by the National Electrical Code (Paragraph 410.21 and Article 250) or Canadian Electrical Code (Rule 30-500 and Section 10). Verify that ground continuity has been established by using an Ohm meter or other suitable testing equipment before energizing the luminaire.
  • Page 7 Apply AC power to the unit. LED indicator on to the luminaire should begin to flash green. If it flashes red; please refer to the Troubleshooting/Maintenance section. Battery will be fully charged within 24 hours (maximum). Emergency luminaire may or may not light at this time, depending on the degree to which battery is charged.
  • Page 8 Tighten the eight captive screws by applying a torque of 2.25 N.m (20 Lb.in) using the sequence shown as in Figure 11. Make sure wires do not pinch between cover and wiring compartment while closing. Apply TLNC4 grease on plugs (3 supplied) in 3 lines, spaced approximately 120 degrees apart, perpendicular to the threads. After applying TLNC4 grease close all unused conduit entries with plugs.
  • Page 9: Wiring Diagrams

    Wiring Diagrams FIGURE 7A: STANDARD WIRING 4 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 2FT FIGURE 7B: STANDARD WIRING 4 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 9 of 43...
  • Page 10 FIGURE 7C: STANDARD WIRING 3 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 2FT FIGURE 7D: STANDARD WIRING 3 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 10 of 43...
  • Page 11 FIGURE 8A: THROUGH FEED WIRING 4 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 2FT FIGURE 8B: THROUGH FEED WIRING 4 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 11 of 43...
  • Page 12 FIGURE 8C: THROUGH FEED WIRING 3 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 2FT FIGURE 8D: THROUGH FEED WIRING 3 WIRE CONNECTION LAyOUT WITH WIRE NUTS: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 12 of 43...
  • Page 13 FIGURE 9A: STANDARD WIRING 4 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 2FT FIGURE 9B: STANDARD WIRING 4 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 13 of 43...
  • Page 14 FIGURE 9C: STANDARD WIRING 3 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 2FT FIGURE 9D: STANDARD WIRING 3 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 14 of 43...
  • Page 15 FIGURE 10A: THROUGH FEED WIRING 4 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 2FT FIGURE 10B: THROUGH FEED WIRING 4 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 15 of 43...
  • Page 16 FIGURE 10C: THROUGH FEED WIRING 3 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 2FT FIGURE 10D: THROUGH FEED WIRING 3 WIRE CONNECTION LAyOUT WITH FIXED SCREW TERMINAL: 4FT Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 16 of 43...
  • Page 17 FIGURE 11: SCREW TIGHTENING SEqUENCE Recommended Appleton™ Cable Connectors Refer table below: Table 5: Compatible Cord Grips Appleton Part Number Recommendation CG3150 Suitable for through wiring using either side (2 CG on either side) CG6250 Suitable for through wiring using either side (2 CG on either side) CG5075 Suitable for through wiring using either side (2 CG on either side) CG3150S...
  • Page 18 5. Tighten the threaded locknut (gate) until tight. FIGURE 13: RIGMASTER 2FT SERIES LUMINAIRE WITH SAFETy CABLES FIGURE 14: RIGMASTER 4FT SERIES LUMINAIRE WITH SAFETy CABLES Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 18 of 43...
  • Page 19: Functional Testing

    Automatic Testing System for Battery Management Module Functional Testing • Functional test starts within 24 to 45 hours after the initial power up of the module. • Automatic self-diagnostic test occurs every 14 days after the aforementioned functional test and lasts for five (5) minutes. •...
  • Page 20 FIGURE 15: LUMINAIRE VIEWS (DISCONNECTION METHOD) Emergency Duration Setting The Rigmaster LED Luminaire with Emergency Battery Backup can be configured for two levels of emergency backup based on the fixture’s duration setting of either 90 minutes or 180 minutes. The default duration setting can be identified by the character on the part number as show in the example below.
  • Page 21: Fuse Replacement

    While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp, LLC. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. The Appleton and Emerson logos are registered in the U.S. Patent and Trademark Office. All other product or service names are the property of their registered owners.
  • Page 22: Sécurité Du Produit

    650610-000 FEUILLE D’INSTRUCTIONS Instructions d’installation du luminaire à LED Appleton™ Rigmaster™ avec batterie de secours POUR UNE INSTALLATION CORRECTE ET EN TOUTE SÉCURITÉ DE CE PRODUIT, VEUILLEZ LIRE LES INSTRUCTIONS SUIVANTES. Sécurité du produit Définition des termes de mise en garde DANGER indique une situation dangereuse qui, si elle n’est pas évitée, entraînera des blessures graves, voire mortelles.
  • Page 23: Applications/Usage Prévu

    AVIS : • Ne touchez pas au LEDs, au risque de laisser des dépôts huileux, sources de points chauds et d’éventuelles défaillances prématurées. • La lentille du LED doit être nettoyée périodiquement de l’extérieur uniquement avec un chiffon humide pour maintenir l’efficacité de l’éclairage •...
  • Page 24: Dimensions/ Détails

    Dimensions/ Détails DIMENSION DU LUMINAIRE FIGURE 1: RIGMASTER 2 PIEDS LUMINAIRE AVEC BATTERIE DE SECOURS FIGURE 2: RIGMASTER 4 PIEDS LUMINAIRE AVEC BATTERIE DE SECOURS Instructions générales de montage 1. Assurez-vous que l’alimentation est débranchée avant d’installer le luminaire. 2. Déterminez la distance de montage appropriée entre les trous de fixation pour votre application. 3.
  • Page 25: Supports De Fixation

    Supports de Fixation GRAND SUPPORT PIVOTANT (RMHLSB) 1. Assurez-vous que l’alimentation est débranchée et que le circuit est hors tension avant d’installer le support. 2. Déterminer la distance de montage appropriée entre les trous des supports pour votre application. Voir la Figure 3(C). 3.
  • Page 26 SUPPORT FIXE à PROFIL BAS (RMHLPB) 1. Assurez-vous que l’alimentation est débranchée et que le circuit est hors tension avant d’installer le support. 2. Déterminer la distance de montage appropriée entre les trous des supports pour votre application. Voir la Figure 4(C). 3.
  • Page 27: Options De Câblage

    TABLEAU DE COMPATIBILITE DES SUPPORTS DE MONTAGE POUR INSTALLATIONS RETROFIT Tableau-2: Comptabilité des Supports de fixation pour montage ultérieurs Numéro de pièce Appleton Fabriquant Numéro de pièce RMHLSB RMHLPB Grand Support pivotant Support à Profil Bas Crouse Hinds DP1057MTK LTXW4 Dialight LTXW4LP LSXW4...
  • Page 28 Pour le câblage d’alimentation continue : (pour toutes les tailles de conduit) : Ouvrez le compartiment de câblage du luminaire en desserrant les quatre vis imperdables. Laisser le couvercle s'ouvrir pour permettre l'accès au compartiment de câblage. Voir la figure 6. Tirez les fils du circuit d’attaque du côté...
  • Page 29 Pour Série de Luminaires avec Option de Borne à Vis Fixes REMARqUE : Voir la plaque signalétique du produit pour connaître les spécifications du câble d’alimentation. Le bornier peut accepter des câbles 12-22 AWG. Utilisez le calibre de fil approprié en fonction de l’application. Tableau 4: SYSTÈME D'ALEIMENTATION L-N SYSTÈME...
  • Page 30: Méthodes De Câblage

    Méthodes de câblage Méthode de câblage pour connexion à 4 fils 1. Branchez la ligne d’alimentation directe à la borne L’ / écrou de fil. Voir les Figures 7A / 7B / 8A / 8B / 9A / 9B / 10A / 10B, selon le cas.
  • Page 31: Schemas De Cablage

    SCHEMAS DE CABLAGE FIGURE 7A: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 4 FILS AVEC ECROUS DE FIL: 2 PIEDS FIGURE 7B: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 4 FILS AVEC ECROUS DE FIL: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev.
  • Page 32 FIGURE 7C: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 3 FILS AVEC ECROUS DE FIL: 2 PIEDS FIGURE 7D: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 3 FILS AVEC ECROUS DE FIL: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 32 of 43...
  • Page 33 FIGURE 8A: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 4 FILS AVEC ECROUS DE FIL: 2 PIEDS FIGURE 8B: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 4 FILS AVEC ECROUS DE FIL: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 33 of 43...
  • Page 34 FIGURE 8C: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 3 FILS AVEC ECROUS DE FIL: 2 PIEDS FIGURE 8D: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 3 FILS AVEC ECROUS DE FIL: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 34 of 43...
  • Page 35 FIGURE 9A: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 4 FILS AVEC BORNES A VIS FIXES: 2 PIEDS FIGURE 9B: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 4 FILS AVEC BORNES A VIS FIXES: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 35 of 43...
  • Page 36 FIGURE 9C: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 3 FILS AVEC BORNES A VIS FIXES: 2 PIEDS FIGURE 9D: CABLAGE STANDARD, DISPOSITION DE CONNEXION A 3 FILS AVEC BORNES A VIS FIXES: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 36 of 43...
  • Page 37 FIGURE 10A: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 4 FILS AVEC BORNES A VIS FIXES: 2 PIEDS FIGURE 10B: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 4 FILS AVEC BORNES A VIS FIXES: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev.
  • Page 38 FIGURE 10C: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 3 FILS AVEC BORNES A VIS FIXES: 2 PIEDS FIGURE 10D: CABLAGE D’ALIMENTATION CONTINUE, DISPOSITION DE CONNEXION A 3 FILS AVEC BORNES A VIS FIXES: 4 PIEDS Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev.
  • Page 39: Connecteurs De Câbles Appleton™ Recommandés

    FIGURE 11: SEqUENCE DE SERRAGE DES VIS Connecteurs de câbles Appleton™ recommandés Voir le tableau ci-dessous: Tableau-5: Serre-câbles compatible Numéro de pièce Appleton Recommandation CG3150 Adapté pour un câblage traversant utilisant l’un ou l’autre côté (2 CG de chaque côté) CG6250 Adapté...
  • Page 40 FIGURE 13: LUMINAIRE RIGMASTER 2 PIEDS AVEC CABLES DE SURETE FIGURE 14: LUMINAIRE RIGMASTER 4 PIEDS AVEC CABLES DE SURETE Appleton • 1.800.621.1506 • www.appletonelec.com 650610-000 Rev. 03 11/02/20 • Page 40 of 43...
  • Page 41: Test Fonctionnel

    Système de test automatique pour module de gestion de la batterie Test fonctionnel • Le test fonctionnel commence dans les 24 à 45 heures suivant la mise sous tension initiale du module. • L’autodiagnostic automatique a lieu tous les 14 jours après le test fonctionnel susmentionné et dure cinq (5) minutes. •...
  • Page 42: Réglage De La Durée D'urgence

    FIGURE 15: VUES DES LUMINAIRES (METHODE DE DECONNEXION) Réglage de la durée d’urgence Le luminaire à LED Rigmaster avec batterie de secours peut être configuré pour deux niveaux de secours en fonction du réglage de la durée du luminaire, soit 90 minutes ou 180 minutes. Le paramètre de durée par défaut peut être identifié par le caractère du numéro de pièce, comme indiqué...
  • Page 43: Remplacement De Fusible

    Bien que toutes les précautions possibles aient été prises pour garantir l’exactitude et l’exhaustivité de ce manuel, Appleton Grp, LLC. décline toute responsabilité quant aux dommages résultant de l’utilisation de ces informations ou aux erreurs ou omissions éventuelles. Les spécifications sont sujettes à modification sans préavis. Les logos Appleton et Emerson sont déposés auprès du bureau des brevets et des marques déposées des États-Unis (U.S.

Table des Matières