Installation Instructions for Appleton™ Baymaster™ LED Luminaire -
Pendant Mount
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Product Safety
Signal Words Defined
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous
situation which, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury. NOTICE is used to address practices not related to physical injury.
Safety Instructions
WARNING:
• Do not open or remove luminaire with the circuit energized.
• Do not use this luminaire on ungrounded systems. Failure to ground this luminaire can result in an electric shock, which may be fatal.
• Do not use on ungrounded 480 Volt circuits.
CAUTION:
• Do not look directly at the LEDs when energized.
NOTICE:
• Do not touch the LEDs; touching could leave oily deposits, causing hot spots and potential premature failure.
• When installing in a Hazardous Location, it is necessary that the door frame assembly (with lens) be in place and tightened down
properly onto the luminaire. This door frame assembly should also be cleaned periodically to maintain lighting efficiency.
• This luminaire is designed for and should be installed in accordance with the National Electrical Code
and all applicable local codes.
• A brace is required on conduit stems longer than 12 inches. (NEC requirements)
Marine & Hazardous Locations
CAUTION/ATTENTION:
• To reduce the risk of ignition of hazardous atmospheres, disconnect the luminaire from the supply circuit before opening. Keep
tightly closed when in operation.
Pour réduire le risque d'inflammation/explosion en atmosphères explosibles, isoler le luminaire du circuit d'alimentation avant
ouverture. Veillez à ce que le luminaire soit correctement fermé avant la mise sous tension.
• Make sure to tighten unused close-up plugs to 400 in.-lb. after applying TLNC4 grease. TLNC4 grease shall be applied in 3 lines,
spaced approximately 120 degrees apart, perpendicular to the threads.
• Where flexible cord is used, it should be approved for extra hard, wet location usage and shall have a separate ground conductor.
Agency Ratings: (NEC/CEC)
• Class I, Division 2, Groups A, B, C, & D
• Class II, Division 1, Groups E, F, & G
• Class II, Division 2, Groups F & G
• Class III
• Simultaneous Exposure
• Class I, Zone 2 Group IIC
Appleton • 1.800.621.1506 • www.appletonelec.com
650526-001 INSTRUCTION SHEET
• Zone 20, Group IIIC
• Zone 21, Group IIIC
• Zone 22, Group IIIB
• Wet Locations
• Marine Outside Type (Salt Water) (For installation in USA only)
• Type 3R, 4, & 4X
• IP66 & IP67
/Canadian Electrical Code
®
650526-001 Rev. D 05/17/17 • Page 1 of 12