Installation And Setting Instructions; Connection Combinations Of Valves And Electronics - Burkert 1094 Instructions De Service

Masquer les pouces Voir aussi pour 1094:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

All manuals and user guides at all-guides.com
4

INSTALLATION AND SETTING INSTRUCTIONS

4.1

Connection combinations of valves and electronics

Valve type
6021
6022, 6023, 6223
with tag connectors
2821
2832, 2834, 2836
with tag connectors
NOTE
ATTENTION!
Carefully insert the blade of the
screwdriver under the manifold, and
lever it out (Diagram 2).
Turn the manifold to the desired
position.
Insert the manifold into the housing
until it latches in.
Operating Instructions-No. 803 037
Bürkert appliance socket
2506
2508
none
1051
1050
none
The use of the Bürkert Type 1610 power supply is recommended
for all combinations!
When connecting the PHR electronics using the appliance
sockets 2506, 2508, 1050 or 1051, note that the cable length
must be less than 50 m; with longer cables, the 0 - 10V control
will no longer produce a full opening of the valve! This can also
apply to other signals.
The direction of the cable run can be changed in 4x 90° steps
when using the cable plug electronics type 1094-PMR.
Only work on the equipment when all voltages have been
removed!
Ensure that the cables ends do not become twisted!
Control electronics
1094-PHR
1094-PHR
1094-PMR
1094-PHR
1094-PHR
1094-PMR
Diagram 2: Turning the manifold
17