2
Mechanical Installation
Upon Receipt
Please perform the following tasks after receiving the drive:
• Inspect the drive for damage. If the drive appears damaged upon receipt, contact
your supplier.
• Verify receipt of the correct model by checking the information on the nameplate.
If you have received the wrong model contact your supplier.
Installation Environment
For optimum performance life of the drive, install the drive in an environment that
meets the conditions listed below.
Environment
Installation Area
Ambient
Temperature
Humidity
Storage
Temperature
Surrounding Area
Altitude
Vibration
Orientation
I67E-EN
V1000 Quick Start Guide
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles
Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Indoors
°
°
-10
C to +40
C (NEMA Type 1)
°
°
-10
C to +50
C (Open-Chassis Type)
When using an enclosure panel, install a cooling fan or air conditioner
in the area to ensure that the air temperature inside the enclosure does
not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
°
°
-20
C to +60
C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m or less
2
10 - 20 Hz at 9.8 m/s
Install the drive vertically to maintain maximum cooling effects.
2 Mechanical Installation
Conditions
, 20 - 55 Hz at 5.9 m/s
2
7