1 Safety Instructions and General Warnings
Precautions for CE Low Voltage Directive Compliance
This drive has been tested according to European standard EN61800-5-1, and it
fully complies with the Low Voltage Directive. The following conditions must be met
to maintain compliance when combining this drive with other devices:
Do not use drives in areas with pollution higher than severity 2 and overvoltage cat-
egory 3 in accordance with IEC664.
Ground the neutral point of the main power supply for 400 V Class drives.
Precautions for UL/cUL Standards Compliance
This drive is tested in accordance with UL standard UL508C and complies with UL
requirements. The following conditions must be met to maintain compliance when
using this drive in combination with other equipment:
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Use UL-listed copper wires (rated at 75°C) and closed-loop connectors or CSA-cer-
tified ring connectors. For details refer to the instruction manual.
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state
or local codes for wiring. Use a class 2 (UL regulations) power supply for the control
circuit terminal. For details refer to the instruction manual.
This drive has undergone the UL short-circuit test, which certifies that during a short
circuit in the power supply the current flow will not rise above 30,000 amps maxi-
mum at 240 V for 200 V class drives and 480 V for 400 V class drives.
The drive internal motor overload protection is UL listed and in accordance with the
NEC and CEC. The setup can be done using the parameters L1-01/02. For details
refer to the instruction manual.
Precautions for Using the Safe Disable Function
The drive's Safe Disable function is designed in accordance with the EN954-1, safety
category 3 and EN61508, SIL2. It can be utilized to perform a safe stop as defined
by the EN60204-1, stop category 0 (uncontrolled stop by removal of power). Refer to
the instruction manual for details about the application of this function.
6
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles
Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
I67E-EN
V1000 Quick Start Guide