Internal Default Set-Value (C.01) - Burkert 8623 Instructions De Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.3.5 Internal default set-value (C.01)

With the internal set-value default, the set-value is entered and stored as a flow
rate (with time units: h, min, sec). The controller will make use of these set flow
rates.
7.3.5.1 Time units of the Set-values
Set up the time units in hours, minutes or seconds using the upper row of
bars.
Fig. 13: Time units of the set-value
7.3.5.2 Internal set-value
Setting the pre-comma value of the internal set-value
Setting the post-comma value of the internal set-value
NOTE:
16 - 8623
Change the time units
Continue from 7.3.5.2
The setting-up of a set-value can only take place to a value
which corresponds to 625 Hz. Setting a set-value outside of this
limit is not possible.
Time unit = h
Time unit = min
Time unit = s
Increase of the pre-comma value
Proceed to set the post-comma
value
Increase of the post-comma value
Continue from 7.3.8
volume units / h
volume units / min
volume units / s

Publicité

Table des Matières
loading

Table des Matières