Leroy Somer R 200 Installation Et Maintenance page 25

Régulateur
Table des Matières

Publicité

AVR
R200
Troubleshooting chart (continued)
SYMPTOM
Voltage unstable
Response time
too long
KW unbalanced during parallel
operation
No voltage droop
under load (PF=0.8)
KVAR unbalanced between
the alternators
PROBABLE CAUSES
- Frequency unstable (governor)
- Sensing taken on the secondary side of a trans- - Connect the sensing to a separate
former supplying other loads
- P4 or P5 out of adjustment
- Fault in exciter or rotating diode bridge
- Faulty regulator
- P4 or P5 incorrectly adjusted
- Speed regulator response time too long
- Load divider incorrectly adjusted
- Incorrect adjustment of speed regulator voltage
droop
- Voltage droop potentiometer
adjusted to minimum
- CT TI04 does not supply 1A
to its secondary (for In). (if used)
- Pot adjusted to minimum voltage droop
- CT TI04 does not supply 1A to its
- Incorrect wiring of parallel CT
- Incorrect wiring of sensing
- Parallel CT is not on the right phase
SOLUTIONS
- Consult manual for speed adjustment
source
- Adjust P4 and P5
- Check diodes and exciter
- Test or replace
- Adjust P4 or P5
-See manual for speed adjustment
- See engine manual for speed ad justment
- See engine manual for speed adjustment
- Adjust for the desired value
(see paragraph 4.5)
- See paragraph 2.4
-Adjust to desired voltage droop
-Replace by appropriate
- Check the wiring
- Check the wiring
- Check the wiring
27