Current
Voltage
V
I S5.0
I S5.1 [9568]
V
X521.1
S5.0
+
<1>
AI 0
-
X521.2
+/-20 mA
+/-10 V
p4067 [0]
p4066[0] (0)
0
1
<1> Differential input!
For an input signal referred to ground, terminal X521.2 must be connected to reference potential.
Caution:
The voltage between an input (X521.1 or X521.2) and ground may not exceed 35 V.
When the load resistor is switched-in (S5.0 closed), it is not permissible that the voltage between the input terminals exceeds 15 V.
<2> For p4056 = 2, 3, 5 the units are mA.
For p4056 = 0, 4 the units are V.
1
2
DO: TM31
Terminal Module 31 (TM31) – analog input 0 (AI 0)
20 mA
<2>
Offset
Hardware
-20.000...20.000
smoothing
p4063[0] (0.000)
100 µs
A
+
+
D
(0)
Window to suppress noise
Smoothing
0.0...1000.0 ms
p4053[0] (0.0)
0
x
-1
1
otherwise y = y(old)
3
4
<2>
<3>
Analog inputs, type
p4056[0] (4)
p4097[0] (0)
20 mA
0
1
p4097[0] (0)
0, 2
r4052[0]
0
3
0
4 mA
4, 5
1
<2>
Simulation mode
-20.000...20.000
p4098[0] (0.000)
Enable
p4069 [0]
0.0...20.0 %
(1)
p4068[0] (0.0)
y = x
y
if |y - x| > p4068
5
fp_9566_01_eng.vsd
21.03.06 V02.04.00
p4099[1] (4000.00 µs)
Threshold for
wire breakage detection
0.00...20.00 mA
0...1000 ms
p4061[0] (2.00)
p4062[0] (100)
3
T
0
3
<2>
-20.000...20.000
-20.000...20.000
p4057[0] (0.000)
p4059[0] (10.000)
y
[%]
-1000.00...1000.00 %
y
p4060[0] (100.00)
2
x
x
1
-1000.00...1000.00 %
y
1
p4058[0] (0.00)
Scaling
x
1
Reference quantities
x
p2000...r2004
x
2
x
x
1
2
100
%
0
0 %
r4055[0]
1
<3> p4056
= 0: 0 V ... +10 V
= 2: 0 mA ... +20 mA
= 3: 4 mA ... +20 mA with monitoring
= 4: -10 V ... +10 V
= 5: -20 mA ... +20 mA
6
7
Function diagram
SINAMICS S
F03505
"Wire
breakage"
<2>
[%]
y
x
x
2
y
8
- 9566 -