p0115[3] (Drive Object)
Refer to [1020.7]
Ramp-function generator selection
n_set_4
[3060.8]
From the basic ramp-function generator
n_set_5
[3070.8]
From the expanded ramp-function generator
Torque limit reached
[2522.7]
r1407.7
<1>
For p1145 > 0, the ramp-function generator tracking is activated when the torque limiting
responds. This means that the speed controller output only exceeds the torque limit by a
deviation that can be set using p1145.
<2>
For OFF1/OFF3 the ramp-function generator ramp is active. The ramp-function generator is
set (SERVO: to the actual value, VECTOR to the setpoint (r1170)) and stops the drive with
the ramp-downtime (p1121 or p1135). STW1.4 (enable ramp-function generator) is effective
while the drive is being stopped via the ramp-function generator. Depending on the p1115, the
basic ramp-function generator [3060] or the extended ramp-function generator [3070] is
effective. When the function module "extended setpoint channel" (r0108.8 = 0) is not active for
OFF1/OFF3, the down ramp of the basic ramp-function generator is effective (refer to n_set_4
on [3060.8]).
<3>
The interpolator is only effective for clock-cycle synchronous PROFIBUS operation and sign-
of-life received from the master (STW2.12 ... STW2.15).
<4>
Behavior of the response ramp of the torque limiting:
p1145 = 0.0: No ramp-function generator tracking. The ramp-function generator ramp distances itself from the speed actual
value.
p1145 = 1.0: The ramp-function generator ramp remains as close as possible to the speed actual value.
p1145 > 1.0: The ramp-function generator ramp is steeper than for p1145 = 1.0 (higher "speed following error").
<5>
For SERVO, the following applies: Only when the function module "expanded setpoint channel" is activated (r0108.8 = 1).
<6>
The value is only correctly displayed if the drive is enabled.
<101> Pre-assignment of the sampling times in p0115, refer to p0112.
1
2
DO: SERVO, VECTOR
Setpoint channel - ramp-function generator selection, status word, tracking
Enable speed setpoint (from the STW sequence control)
r0898.6
Enable ramp-function generator (from the STW sequence control)
[2501.7]
[2501.7]
n_ctrl n_set 1
1
p1155[C]
(0)
<2>
0
0
n_ctrl n_set 2
p1160[C]
<2>
(0)
Synchronization
No OFF1
&
No OFF2
0
No OFF3
RFG selection
1
p1115
r3812
RFG n_set at the output
0
r1150
RFG tracking intensity
1
0.0...50.0
p1145[D] (1.3)
<4>
[3060.8]
[3070.8]
[3060.8]
[3070.8]
[3080.8]
[3050.8]
3
4
r0898.4
1
p1189.1
x,y
0
x
+
0
1
+
+
0
Interpolator
Expanded setpoint channel
r0108.8
p1189.0
<5>
x,y
x
0
1
0
1
0
Interpolator
Ramp-function generator tracking
Ramp-function generator status word
Bit
Ramp-function generator status word
0
Ramp-up active
1
Ramp-down active
2
Ramp-function generator active
1
3
Ramp-function generator set
4
Ramp-function generator held
5
Ramp-function generator tracking active
6
Maximum limiting active
7
Reserved
8
Reserved
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
5
6
fp_3080_01_eng.vsd
22.03.06 V02.04.00
p0115[3] (Drive Object)
Refer to [1020.7]
<101>
n_ctrl n_set 1/2
<6>
<3>
r1169
x
T1
y
Plot friction characteristic
y
No OFF2
&
No OFF3
t
+
0
n_ctrl n_set sum
x
r1170
T1
y
+
y
1
From the ramp-function
t
generator friction characteristic
[7010.6]
Ramp flattening-off
Ramp-function generator tracking active
r1199.5
RFG ZSW
r1199
r1199.2
[8010.5]
<1>
7
Function diagram
SINAMICS S
[5020.1]
[6030.1]
[8010.5]
[3060.1]
[3070.3]
8
- 3080 -