Accessing the Drive
After making a successful connection to the drive, launch the FE Connect mobile app. The FE
Connect mobile app can be downloaded from the Apple App Store or Google Play depending on the
device being used.
Set-up
The Set-up screen allows for the set-up of additional features of the drive including:
• Drive Output*
• Motor Size*
• Pump Size*
• Underload Sensitivity*
• Underload Off Time
• Minimum Frequency
• Maximum Frequency
* In order to change and use settings from this page for the Drive Output, Motor Size, Pump Size, Underload
Sensitivity, Pressure Sensor Type, Pressure Transducer Range, Pressure Set Point, Duplex Alternator
Functionality, and Steady Flow, the FE Connect DIP switch (SW1, Position 1) on the drive must be "ON".
Otherwise, the drive will default to the settings made via the DIP switches and Underload Sensitivity and
Pressure Set Point rotary knobs on the drive itself.
The Pressure Control portion of the Setup screen allows for configuration
of the Sensor Type, Transducer Range, Primary Setpoint,
and Drawdown functions.
Pressure Control: Sensor Type
This parameter sets which pressure sensor type to use: Switch,
Transducer (PSI), or Transducer (bar).
Default: Transducer (PSI)
Pressure Control: Transducer Range
When using a pressure transducer, this parameter sets the range of the
transducer connected to the drive.
Default: 100 (PSI)
Pressure Control: Primary Setpoint
When using a pressure transducer, this parameter sets the system
pressure set point that the controller will regulate to.
Default: 50 PSI
Maximum: (Pressure Transducer Range) – 5 PSI
Pressure Control: Drawdown
This selection enables or disables the drawdown function. Drawdown
allows the drive to regulate to the Pressure Setpoint and remain off until
the Cut In Setpoint is reached.
Pressure Control: Cut In Setpoint
Also known as drawdown, this parameter sets the pressure to which the
system pressure must be reduced before the controller will begin to run.
Default: 40 PSI
Minimum: 5 PSI
1 PSI
• Pressure Sensor Type*
• Pressure Transducer Range*
• Pressure Set Point*
• Drawdown / Cut-in Pressure
• Duplex Alternator Functionality*
• Moisture Sensor
• Bump Mode
Minimum: 100 PSI
Minimum: 5 PSI
Maximum: (Pressure Setpoint) –
SubDrive/MonoDrive Connect
Maximum: 300 PSI
• Large Tank Mode
• Aggressive Bump
• Broken Pipe Detection
• Steady Flow*
• Units (hp or kW)
Pressure Control
Sensor Selection
Transducer Range
Primary Setpoint
Drawdown Enable
Cut In Setpoint
33