Application And Function Of Ssm Relay; Application And Function Of Sbm Relay - Wilo Stratos GIGA2.0-I Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

13.1
Application and function of SSM
relay
13.2
Application and function of SBM
relay
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
The contact of the collective fault signal (SSM, potential-free changeover contact) can be
connected to a building automation system. The SSM relay can either switch on only in case
of fault or for faults and warnings. The SSM relay can be used as a normally closed contact
or a normally open contact.
When the pump is without power, the NC contact is closed.
If there is a fault, the contact at NC is open. The converter bridge to NO is closed.
In the "Settings" menu 
, select
1.
"External interfaces"
2.
"SSM relay function".
Possible settings:
Selection option
Only fault (factory setting)
Faults and warnings
Table 34: Function SSM relay
After confirming one of the selection options, the SSM trigger delay and SSM reset delay
are entered.
Setting
SSM trigger delay
SSM reset delay
Table 35: Trigger and reset delay
Triggering of the SSM signal after occurrence of a fault or a warning is delayed.
Resetting of the SSM signal after occurrence of a fault or a warning is delayed.
Trigger delays are used so that processes are not influenced by very short fault or warning
messages.
If a fault or a warning is fixed before the end of the set time, there will be no message to
SSM.
A set SSM trigger delay of 0 seconds immediately reports faults or warnings.
If an error message or warning message occurs only for a brief duration (e.g. in case of a
loose contact), the reset delay prevents the SSM signal from fluttering.
NOTICE
SSM trigger and SSM reset delay is set to 5 seconds as a factory setting.
SSM/ESM (collective fault signal/individual fault signal) in twin-head pump operation
SSM The SSM function must preferably be connected to the main pump.
The SSM contact can be configured as follows: the contact reacts either only in the
event of a fault or in the event of a fault and a warning.
Factory setting: SSM only reacts in the event of a fault.
Alternatively or additionally, the SSM function can also be activated on the standby
pump. Both contacts work in parallel.
ESM The ESM function of the twin-head pump can be configured on each twin-head
pump head as follows:
The ESM function on the SSM contact only signals faults of the respective pump (indi-
vidual fault signal). In order to detect all faults of the two pumps, the contacts must be
assigned in both drives.
The contact of the collective run signal (SBM, potential-free changeover contact) can be
connected to a building automation system. The SBM contact signals the operating status
of the pump.
Function SSM relay
SSM relay connects only in case of fault. Fault means:
The pump is not running.
SSM relay connects only in case of fault or a warning.
Range in seconds
0 s ... 60 s
0 s ... 60 s
en
193