Code
Warning
Additional information about causes and remedy:
Control functions impaired. A replacement function is active.
565/
Signal too strong at analogue input AI1, AI2,
566/
AI3 or AI4.
593/
596
Additional information about causes and remedy:
The signal is processed with the maximum value.
569
Configuration missing.
Additional information about causes and remedy:
Pump operating in replacement mode.
570
Electronic module too hot.
Additional information about causes and remedies:
The electronic module must adjust the pump's operation in the event of noticeable overheating
to prevent damage to electronic components.
571
Twin-head pump connection interrupted.
Additional information about causes and remedy:
Pump function slightly impaired. The motor head meets the pump function up to the performance limit.
573
Communication to display and operating
unit interrupted.
Additional information about causes and remedies:
The display and operating unit is connected to the pump's electronics on its rear side via a ribbon cable.
574
Communication to CIF module interrupted.
Additional information about causes and remedy:
The CIF module is connected to the pump in the terminal room via four contacts.
575
Remote control not possible by radio.
Additional information about causes and remedy:
Pump function not impaired.
If a software update does not eliminate the issue, contact Service.
578
Display and control unit defective.
Additional information about causes and remedy:
The display and operating unit is available as a spare part.
579
Software for display and control unit in-
compatible.
Additional information about causes and remedy:
Pump function not impaired.
If a software update does not eliminate the issue, contact Service.
580
Too many wrong PIN entries.
Additional information about causes and remedies:
An incorrect PIN has been entered more than 5 times.
For safety reasons, further connection attempts are prevented without a restart.
582
Twin-head pump is not compatible.
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
Cause
The available signal is significantly
over the expected maximum.
Pump configuration is missing.
Permissible temperature of the
electronic module is exceeded.
The connection to the twin-head
pump partner cannot be made.
Internal communication to display
and operating unit interrupted.
Internal communication to the CIF
module interrupted.
The Bluetooth radio module is
faulty.
A fault in the display and operating
unit has been identified.
Display and operating unit cannot
communicate correctly with the
pump.
Too many connection attempts with
wrong PIN.
Twin-head pump partner is not
compatible with this pump.
Remedy
Check input signal.
Configure pump. Software update is
recommended.
Ensure permissible ambient temper-
ature. Check electronic module
ventilation. Keep cooling fins free of
deposits.
Check power supply of the twin-
head pump partner, cable connec-
tion and configuration.
Check ribbon cable contacts.
Check/clean contacts between CIF
module and electronic module.
Software update is recommended.
Contact Service.
Replace display and operating unit.
Software update is recommended.
Disconnect power supply from the
pump and switch it on again.
Select/install appropriate twin-head
pump partner.