Limit Indication Depending On Setting Or Sensor Signal - Helios EUR EC Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification EUR EC
Example indication by relay "K1":
not inverted
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
1
0
1
0
A Modulation
If "Level min." is higher than "Level max.", the "Level max." switching point is without hysteresi.
9.10.2

Limit indication depending on setting or sensor signal

Same procedure for analogue inputs "E1" and "E2".
Limits
OFF
Lmt E1 Function
Limits
- - - - -
Lmt E1 min
Limits
- - - - -
Lmt E1 max.
Limits
- - - - -
Lmt E1 Hyst.
L-BAL-E274-GB 1914 Index 003
A
min
max
100 %
A
max
min
100 %
11.05.2007
v_grenzwert_ausst_k1_ni.vsd
Following functions can be allocated to the limit indication
OFF
Fault
(1L)
Message
(2L)
Filter error
(3L)
Filter Message
(4L)
In the IO setup, a separate relay can be allocated independent of these settings.
Both values for E1 ("E1 min" and "E1 max") can be set independent of each other and
act on a relay together if correspondingly programmed. If a function is activated or if a
relay is allocated, both settings ("min" and "max") are initially at "OFF".
Work can be carried out with one as well as with both limit indicators.
The same setting applies to "E2 Min." and "E2 Max.", described below for "E1".
Undercutting the signal ("E1 Min").
If the signal undercuts the set value "E1 min", this is reported until the set value (plus
adjustable hysteresis) has been exceeded once again.
Exceeding the signal ("E1 max").
If the signal exceeds the set value "E1 max", this is reported until the set value (minus
hysteresis) has been undercut once again.
E1 Hysteresis
Hysteresis adjustment in the unit of measure of the programmed input signal.
Inverting
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
1
0
1
0
max
A Modulation
no function (factory setting)
Limit alarm alternating with actual value display Is listed in the proto-
col as an alarm.
Indication with the centralized fault of a programmed relay (IO alloca-
|
|
tion Function
2K
).
Is listed in the protocol as a message. There is no alternating mes-
sage on the actual value display and no message via alarm relay.
|
|
Like function
1L
with fault message "Filter"
|
|
Like function
2L
with fault message "Filter"
Part.-No.
79/117
Programming
A
min
max
100 %
A
min
100 %
11.05.2007
v_grenzwert_ausst_k1_i.vsd