Installation and Operating Specification EUR EC
9.8.3
Save user settings restore with PIN 9090
Controller Setup
OFF
Save User Setup
Information
By entering the "PIN 9095" in the "PIN" menu of the "Start" menu group the device is reset to the as-
delivered state (except for the saved events in the "Protocol"menu).
Any changes that have been made to the settings are thus lost.
9.8.4
Sensor Alarm ON / OFF
The sensors at the analog inputs "E1 Analog In" and "E2 Analog In" (if sensor 2 is activated) are
monitored.
In case of an interruption or short-circuit in the sensor conductor, or in case of measured values that
lie outside of the device's measurement range, a time-delayed fault indication takes place.
Function only in controller mode (from
Controller Setup
ON
Alarm sensors
Controller Setup
OFF
Alarm sensors
L-BAL-E274-GB 1914 Index 003
The individually made device configurations (User Setting) can be saved here (corre-
sponds to PIN 9091).
By entering PIN 9090 the individually made device configurations can be reestablished
(9090 Start - PIN Input).
A file (userconf.csv) is generated and saved on the main drive (root directory) when
saving the user setting.
The data can be accessed via the ZAset program.
2.01
)!
With "Alarm Sensors" = "ON" (factory setting). Indicated
sensor disturbances are displayed as "Alarm" alternating to
the actual value and stored in the menu of "Protocol".
A programmed alarm relay (factory setting relay K2) indicates
the sensor failure.
With "AlarmSensors" = "OFF" areindicated sensor disturban-
ces as "Message" alternating to the actual value and stored in
the menu of "Protocol".
Part.-No.
48/117
Programming
Sensor 1
Sensor 1