Installation and Operating Specification EUR EC
Setting
50 %
Set Internal1
Setting
- - - - -
Set Internal2
Setting
15 %
Min. Speed
Setting
100 %
Max. Speed
Setting
ON
Set external1
Diagram setting signal and output voltage (Idealized principle diagram)
MODBUS Out: speed setting over MODBUS
Analog Out: speed setting over analog output 0 - 10 V
Si Signal
L-BAL-E274-GB 1914 Index 003
Set Internal1
Setting range manual speed setting: 0...100 %
Factory setting: 50 %
Set Internal2
Setting "Set Intern2" e.g. reduced value for night operation.
Switch over Internl 1/2 over external contact (display as long as no allocation is carried
|
|
out:
- - - - -
IO Setup).
Min. Speed
Setting range: 0... "Max. Speed"
Factory setting: 15 %
Max. Speed
Setting range: 100 %... "Min. Speed"
Factory setting: 100 %
Set external1
"ON" (factory setting) = speed setting by external Signal
"OFF" = Setting "Set Intern1"
100
90
80
70
60
50
40
Min.
30
20
10
0
1
2
3
4
5
6
10
9
8
7
6
5
4
0
2
4
6
8
10
12
20
18
16
14
12
10
8
4
5,6
7,2
8,8
10,4
12
13,6 15,2 16,8 18,4
20
18,4 16,8 15,2 13,6
12
10,4
Part.-No.
27/117
"Min. Speed"... "Max. Speed"
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
Si
7
8
9
10
0 – 10 V
3
2
1
0
10 – 0 V
14
16
18
20
0 – 20 mA
6
4
2
0
20 – 0 mA
20
4 – 20 mA
8,8
7,2
5,6
4
20 – 4 mA
28.03.2013
v_out_cxe_master_101.vsd
Programming