Installation and Operating Specification EUR EC
Setting
- - - - -
2.Setpoint 2
Setting
100.0 Pa
2. Pband 1
Setting
0 %
2. Min. Speed
Setting
100 %
2. Max. Speed
Setting
OFF
1. Manual mode
Setting
100 %
1. Speed man.
Function extension for digital inputs "D1" and "D2" in operation with second control circuit
D1 / D2 Function
E1 / E2
(4D)
2. Setpoint 1/2
(9D)
2.Setp+Pband1/2
(16D)
* Detailed description
Following restrictions apply for the control circuit 2:
The "Manual Mode" function in the "Setting" menu group only influences control circuit 1!
The Limit fuction (
neously.
The "Max. Speed" setting by a digital input (
control circuits. I.e. at "1.Max. Speed" and at "2.Max. Speed".
The controller configurations (KP, KI, KD, TI
circuits. Fine adjustment is possible for each control circuit by the separate "Pband" setting.
L-BAL-E274-GB 1914 Index 003
2.Setpoint 2
Setpoint 2 for control circuit 2
Setting "Setpoint 2" e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out
|
|
Display:
- - - - -
IOSetup).
2. Pband 1
Pband 1 for control circuit 2
Setting range: in measuring range of sensor
Factory setting: 100 Pa
2. Min. Speed
Minimal Speed for control circuit 2
Setting range: 0... "2. Max. Speed"
Factory setting: 0 %
2. Max. Speed
Maximal Speed for control circuit 2
Setting range: 100 %... "2. Min. Speed"
Factory setting: 100 %
Manual mode
Manual mode for control circuit 1
"OFF" = automatic control as function of the set parameters (Factory setting)
"ON" = automatic control without function, speed setting in menu "Speed manual"
Speed manual
Speed Manual mode for control circuit 1
Setting range: 0... "1. Max. Speed"
Factory setting: 100 %
Description *
The output for control circuit 2 is set additionally to "A2" to "A1" (regardless of the
|
programmed function for
A1
switching.
for control circuit 2: Switch over "Setpoint 1" / "Setpoint 2"
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function, "Setting" additionally lists the parameter: "2.Pband 2 for
control circuit 2"
IO Setup / Digital Inputs "D1" / "D2"
|
|
IO Setup
3D
and Controller Setup) influences both control circuits simulta-
Part.-No.
17/117
|
). Control circuit 1 has no output for the duration of the
|
|
IO Setup
11D
) simultaneously influences both
Controller Setup) are identical for both control
Select operation mode