Installation and Operating Specification EUR EC
9.2
Temperature control
9.2.1
Basic setting
Main menu
Setting
Protocol
Base setup
Controller Setup
IO Setup
Base setup
2.01
Mode
Base setup
TF
E1 Analog In
Base setup
20.0 °C
E1 Offset
L-BAL-E274-GB 1914 Index 003
2.01
...
2.05
2.01
...
2.05
Base setup
The sensor input is factory set in modes of group
Other settable sensors:
PT1000
•
at terminals
MTG-120V (type designation for active sensor with 0 - 10 V output, connection to
•
terminals
"E1"
,
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
•
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
Example with a 0 - 10 V sensor and 0 - 100 °C measurement range:
E1 Analog In = 0 - 10 V, E1 Unit = °C, E1 Decimals = 1, E1 Min. = 0,0 °C, E1 Max. =
When selecting sensors with active signal, the setpoint and the Pband are automati-
Sensor calibration with calibrated comparison device.
The current "E1 Actual" is displayed including the offset set here.
Mode
Mode selection e.g.
E1 Analog In
(sensor type KTY81-210).
Measuring range: -50.0...+150 °C
Connection terminals: "E1" and "T"
and
, (measuring range -50.0...+150 °C)
"E1"
"T"
"24 V"
"GND"
and
, measuring range: -10...+120 °C)
order to display the actual value correctly.
100,0 °C,
cally set to the 1/2 measuring range.
E1 Offset
Part.-No.
30/117
Programming
2.01
2
to sensors of the "TF" type series