Installation and Operating Specification EUR EC

6 Select operation mode

6.1

Mode and signal input

Information
Simple installation is possible through the selection of the preprogrammed mode of operation (
Start-up)
This determines the basic function of the device; factory setting
0 - 10 V signal). The controller configuration is automatically carried out during selection of the
application related mode of operation. The factory presets in accordance with the mode of operation
are based on many years of experience, which is suitable for many applications. Under special
circumstances, these can be individually adapted (
"Controller Configuration").
The purpose of the device is to reach and maintain the target values set. To accomplish this, the
measured actual value (sensor value) is compared with the adjusted target value, and the controlled
value (modulation) is deduced from this.
By selection of the mode the function for control circuit 1 is determined, this influences the following outputs (factory setting):
1. Analog output
"A1"
0 - 10 V with function
2. MODBUS Master interface
Signal or Sensor
Mode
Signal: 0 - 10 V, 0 - 20 mA, 4 -
1.01
20 mA (E1)
1.02
2.01
* Sensor TF.. / LTR, LTK, LTA
2.03
Sensor TF.. / LTR, LTK, LTA
Sensor TF.. / LTR, LTK, LTA
2.04
*
Sensor TF.. / LTR, LTK, LTA
Sensor TF.. / LTR, LTK, LTA
2.05
*
Sensor TF.. / LTR, LTK, LTA
4.01
* Sensor DSG../ LDF500
1 x Sensor DSG../ LDF500
4.02
1 x Sensor TF.. / LTK, LTA
6.01
* Sensor MAL10 / LGF10
1 x Sensor AFS 0-10 V
8.01
1 x Sensor AFS 0-10 V
* Operation with a second control circuit possible
L-BAL-E274-GB 1914 Index 003
|
|
2A
(
Electrical installation).
+
with function
"1A"
"1B"
Input
(input)
E1
-
E1
E1
E1
E2
E1
E2
E1
E1
E2
E1
E1
E2
Operating Instructions / Controller Setup:
|
|
2A
(
Electrical installation).
Speed controller with input for Setting signal, two step operation
(Factory setting)
Manual speed controller with direct setting by the ▼+ ▲ keys
(0 - 100 % or in 1 - 5 steps)
Temperature control airconditioning and refrigeration
(preset Setpoint 20.0 °C, P-band 5.0 K)
Temperature control with additional functions (shutter and heat-
ing)
Temperature control with two sensors, comparison or average
Temperature control with two sensors differential temperature
Pressure control for ventilation systems
Pressure control depending on outdoor temperature
Air velocity control e.g. clean room
Absolute humidity control with 2 sensors (humidity difference)
Part.-No.
14/117
Select operation mode
1.01
= speed controller (activation via
Function