4.3 ELECTRICAL CONNECTION INSTRUCTIONS

Always ensure that the appliance is not powered before working on it. All the connections must be
disconnected.
-
Use a shielded cable with a limit operating temperature > +80°C.
-
Under normal con di tions of use, a shielded cable of 0.75 mm
for signal transmission.
-
Do not install the line close to high voltage or high frequency cables.
-
If adjacent laying is unavoidable, keep a minimum distance of 30 cm.
-
Connect the shielding to earth.
-
Use a quality power supply (filtered and regulated).
- Do not open or cable the sensor when powered.
- It is essential that a 100 mA fuse be used for the power supply.

4.3.1 Mounting and connection of the EN 175301-803 connector

-
Remove part [3] from part [2].
-
Unscrew the cable gland [5].
-
Insert cable into part [2] via cable gland.
-
Wire part [3] (see below)
-
Replace part [3].
-
Tighten the cable gland [5].
-
Place gasket [4] between the connector and the
fixed connector of the 8223.
-
Connect the connector to the 8223.
-
Tighten screw [1] to ensure tightness and correct electrical contact
Always check the connection of the connectors to ensure correct opera-
tion of the appliance.
8223
INSTALLATION
2
4-20 mA output
Not connected
15
2
section is sufficient
2
3
4
5
6
L-
3
L+
1
(12-30 VDC)
1