4.1 MOUNTING INSTRUCTIONS
4.1.1 Temperature-pressure diagram
The sensor and the fitting in which it is installed have limited operating temperatures and
pressures. The diagram hereunder shows the operating range of the 8223-fitting assem-
bly, for each fitting material:
A: Operating range of the assembly 8223+fitting
4.1.2 Installation recommendations
Choose a mounting position which avoids the building of air bubbles or cavities within the
finger orifice.
1
Position 1: horizontal or vertical mounting onto a pipe.
Position 2: mounting on a vessel without stirring
Position 3: mounting on a vessel with stirring
- When dismounting the sensor from the pipe, take all the precautions
related to this process.
- Ensure the fluid passage orifice is in the direction of the flow.
8223
INSTALLATION
A
P [bar]
8
7
6
5
4
PVC
3
2
PP
1
0
0
+20 +40 +60 +80 +100
-10
13
Metal
PVDF
T [°C]
3
2