Physical Installation; Environmental Requirements - Franklin Electric SubDrive 15 Manuel Du Propriétaire

Masquer les pouces Voir aussi pour SubDrive 15:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Physical Installation

Environmental Requirements

Risk of damage to Drive
installation, or environment.
Handle with care to prevent damage to the plastic components.
Do not mount VFD on equipment with excessive vibration.
Install in a location where temperature is within the range of product rating.
Mount VFD vertically (top up) for proper heat dissipation.
Do not mount VFD in direct sunlight or near other heat sources.
Do not install in corrosive environments.
Installation of non-approved screening may damage the drive and/or reduce output.
The SubDrive/MonoDrive controller is intended for operation in ambient temperatures from
-13 °F to 122 °F (-25 °C to 50 °C). Use the following recommendations when selecting a location to
mount the drive:
The unit should be mounted on a structure such as a wall
or post capable of supporting the weight of the unit.
The SubDrive/MonoDrive electronics are air-cooled. Allow
at least 6 inches (15.24 cm) of clearance on each side and
below the unit for air flow.
The mounting location should have access to 208/230 VAC
electrical supply and to the motor wiring. To avoid possible
interference with other appliances, refer to
"Cable Routing" on page
Special Considerations for Outdoor Use
The SubDrive/MonoDrive is suitable for outdoor use with a
NEMA 3R rating; however, the following considerations should
be made when installing the controller outdoors:
The unit must be mounted vertically with the wiring end
oriented downward, and the cover must be properly
secured (also applies to indoor installations).
Mount the drive on a surface or back plate no smaller than
the outer dimensions of the enclosure.
NEMA 3R enclosures are capable of withstanding downward-directed rain only. Protect from
hose-directed or sprayed water as well as blowing rain. Failure to do so may result in controller
failure.
Install away from direct sunlight or locations subject to extreme temperatures or humidity.
Use appropriate screening for the air inlet and outlet when installed in areas where insect or
small animal intrusion is an issue. Refer to
Screens should be cleaned on a regular basis to ensure proper airflow.
,
or malfunction can occur due to improper handling,
19.
"Accessories" on page 54
INSTALLATION AND SETUP
Physical Installation
for ordering information.
17

Publicité

Table des Matières
loading

Table des Matières