Wiring Examples - Burkert 8071 Manuel Utilisateur

Masquer les pouces Voir aussi pour 8071:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.3.3.

Wiring examples

See the 8025 Universal instruction manual to correctly
position the selectors.
NPN
L-
L+
Fig.6
Example of connection between the 8071 and a transmitter
8025 Universal, 13-30 VDC, wall-mounted version.
14
SOURCE SINK
PE PE
Iout L+ L-
P-
P+
PE
CURRENT
Supply
PULSE
13..30Vdc
OUTPUT
1
PULSE INPUT
-
SUPPLY
2
+
NC
3
4
NC
NC
COIL
PE
FLOW SENSOR
SENSOR SUPPLY
1
+5V
2
+12V
3A/230VAC
3
L+
8025 Universal
english
See the 8025 Batch instruction manual to correctly position
the selectors:
If the supply voltage of the 8025 Batch is lower than 24V,
position the switch "Sensor Supply" on L+.
If the supply voltage of the 8025 Batch is higher than
24V, position the switch "Sensor Supply" on (L+) -12V.
SENSOR
INPUT LOAD
3
1
2
39K
2.2K
470
COIL
PNP
NPN
NPN
PNP
FLOW SENSOR
VDC
L+
L-
NPN
Fig.7
Example of connection between the 8071 and a transmitter
8025 Batch, 12-30 VDC, panel-mounted version.
Type 8071
Installationandwiring
X
NPN SENSOR
BINARY
1 PULSE INPUT
2 -
SUPPLY
3 +
4 NC
COIL SENSOR
NC
L+
1
2
3
4 PE
SENSOR SUPPLY
3A/230VAC
FLOW SENSOR
8071
8025 Batch
Supply
12..30Vdc
COIL
NPN
SENSOR INPUT
(L+)-12V

Publicité

Table des Matières
loading

Table des Matières