LEM MachineTest 204 Manuel D'utilisation page 14

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

MEASUREMENTS
STEP 2
Prepare the object to be tested
Make sure tested object to be disconnected from mains voltage!
-
-
Switch "on" main switch of tested object as well as other switches, in
order to test all electronic parts of tested object!
-
Short all live terminals of tested object (L1, L2, L3, N).
STEP 3
Carry out the measurement
Connect one test lead to shorted live terminals using alligator clip.
-
Connect the other test tip to PE terminal of tested object, see the figure
-
below.
Fig. 09: Connection of test leads
Press the START/STOP key to start the measurement, wait until result
-
is stable then read displayed result.
Press the START/STOP key to stop the measurement.
-
Disconnect test leads.
-
Write down read result.
-
− ∼
13
ATTENTION !
(only if tested machine is grounded i.e.
not isolated)
Test lead connection to "- ~" test
terminal should be connected to the
housing (PE terminal) otherwise the test
result will be below the actual value
(5MOhm in parallel) !

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sa 8100 z

Table des Matières