MEASUREMENTS
STEP 2
Compensate resistance of test leads
Connect alligator clip to a test tip.
-
Short free test tip and alligator clip.
-
Select U
-
carried out later).
Press the START/STOP key and set display value to 0.00 V adjusting the
-
TEST LEADS COMPENSATION button.
Press the START/STOP key again to stop the measurement. The
-
instrument is now ready for carrying out measurements.
STEP 3
Carry out the measurement
-
Connect one test lead to one test point of tested object (PE terminal or a
part of conductive housing) using alligator clip, see the figure below.
Connect the other test tip to another test point of tested object (assure
-
good contact).
Fig. 07: Connection of test leads
Press the START/STOP key to start the measurement, wait 10 s until
-
acoustic signal (beep) is effected, then read displayed result and press
the START/STOP key to stop the measurement.
Disconnect test leads.
-
Write down read result.
-
Note!
Voltage drop (U
carried out whenever test result is to be entered in to the measurement protocol
according to EN 60204 requirements. Result is in (V).
Resistance (R
PE
carried out when local prescriptions restrict resistance of the protective conductor or if
the instrument is used for appliance testing. (e.g.: DIN VDE 0701)
function (regardless of which function - U
PE
) measurement is required by the EN 60204 standard and shall be
PE
) measurement is not required by the EN 60204 standard and shall be
11
or R
PE
PE
will be