Parameter
− In ON/OFF mode, the heating/cooling request is always active (relay closed)
if the T3 (comfort) time period is active.
− In OTBus mode, the heating request is always active (only with the external
probe connected to the boiler or the external web probe via the APP) and
the heating setpoint temperature is calculated using the external probe
value only. The value set for parameter 26 (tSFt) is subtracted from the
heating delivery setpoint calculated by RiCLOUD (tSEt), only in AUTO
operating mode, during the T2 (economy) or T1 (anti-freeze) time period.
9
This function uses one RiCLOUD only.
28 FCLO
29 CHOt
30 btLt
31 HHbO
00 EHIt
Description
Time display setting. Default set to 24-hour
clock.
The format can be set to the 12- or 24-hour
clock.
Setting the parameter to 12H, the field is
display in the 12-hour a.m./p.m. format.
Enabling/disabling
(available with OTBus connection between the
WiFi Box and the boiler or the RF receiver and the
boiler or RiCLOUD and the boiler, if provided for by
the OTBus protocol). Default set to ON. This value
can be set to ON or OFF. Setting this parameter to
OFF, RiCLOUD thermostat does not consider the
heating request via OTBus to the boiler.
Enable/disable backlighting.
ON/OFF Configurable value: set to OFF so that
the backlighting will not switch on at every
operation thus making the batteries last
longer. Press the button SET/PROG or ESC/
MODE to go back to the HOME page.
Maximun boilerl central heating temperature
setpoint (available with OTBus connection
between the WiFi Box and the boiler or the
RF receiver and the boiler or RiCLOUD and the
boiler, if provided for by the OTBus protocol).
The value can be set between 80°C and 40°C (for
high temperature heating) or from 45°C to 20°C
(for low temperature heating). This parameter
has to be set by the Authorised Service Centre.
Press the SET/PROG button or ESC/MODE to
return to the HOME screen.
85
heat
request via
OTBus