Parameter
Description
23 LEgI
Enabling
the
anti-legionella
function
for boilers with domestic hot water tank
(available with OTBus connection between
the WiFi Box and the boiler or the RF receiver
and the boiler or RiCLOUD and the boiler, if
provided for by the OTBus protocol). Default
set to OFF .
This value can be set to ON or OFF . By setting
this parameter to ON; every 20 domestic hot
water request cycles a request to replenish
the tank is sent with a domestic hot water
delivery setpoint of 65°C. If the 20 cycles
have not be performed within one week, a
request to replenish the tank is sent with a
domestic hot water delivery setpoint of 65°C
on Saturday at 1.00 a.m.
24 CLOC
Enabling domestic hot water timer for boilers
with domestic hot water tank (available with
OTBus connection between the WiFi Box and
the boiler or the RF receiver and the boiler or
RiCLOUD and the boiler, if provided for by the
OTBus protocol).
Default set to OFF . This value can be set to
ON or OFF . Setting this parameter to ON, the
domestic hot water time periods can be
programmed, as explained in "3.8 Setting
the DHW time program" page 72.
26 tSFt
The parameter will only be shown if the
SEnS parameter is OFF (available with OTBus
connection between the WiFi Box and the
boiler or the RF receiver and the boiler or
RiCLOUD and the boiler, if provided for by
the OTBus protocol). Default set to 10°C. The
value can be set from 1°C to 20°C. The value
set for this parameter will be subtracted from
the heating delivery setpoint calculated by
RiCLOUD (tSEt), only in AUTO
operating
mode, during the T2 (economy) or T1 (anti-
freeze) time period.
27 SEnS
Enabling/disabling room sensor to activate
pure climate control (thermoregulation from a
single external probe). Default set to ON. This
value can be set to ON or OFF . In AUTO
,
MAN
and PARTY
operating modes only,
by setting this parameter to OFF the heating/
cooling request is processed as follows:
84