8.5
Switch-on sequence
1.
Attach the keypad
2.
Ensure that controller inhibit is active after mains connection.
3.
Switch on the mains
4.
The keypad is in "Disp" mode after approx. 2 s and indicates the
output frequency (C0050)
5.
Change to the menu
6.
Change to the
drive
7.
Adapt the terminal configuration to the wiring (C0007)
Lenze setting: -0-, i. e.
E1: JOG1/3 JOG frequency selection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW operation
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
Lenze setting: 5.00 s
Lenze setting: 5.00 s
11.
Set the deceleration time T
Lenze setting: 5.00 s
Lenze setting: 5.00 s
12.
Activate the control mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characterisitic control (C0014 = 2)
13.
Adapt the voltage/current range to the analog setpoint (C0034)
Lenze setting: -0-, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
14.
Enter the motor data
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
E
Motor cosϕ (C0091)
Lenze setting: Depending on the controller
L
Commissioning - vector control
The following Instructions apply to controllers equipped with a Standard-I/O function module and a
three-phase AC motor which has been selected accordingly.
ALL
(^ 39)
f
mode to configure the basic settings for your
(C0012)
ir
(C0013)
if
d
c
b
e
j g f k i h PS
m n o
p
q
r
Hi
Lo
z
d
c
w x
j g f k i h PS
y
m n o
q
r
Hi
Lo
z
d
c
w x
j g f k i h PS
m n o
y
q
r
Hi
Lo
[f]
C0011
C0010
0 %
z
d
c
w x
jgfkih PS
mno
y
q r
Hi
Lo
z
d
c
w x
j g f k i h PS
m n o
y
q
r
Hi
Lo
EDK82EV903 DE/EN/FR 1.0
Commissioning
Vector control
Note
Terminal X3/28 = LOW
The menu
USEr
is active
a
Hz
The most important codes listed in the menu
are explained in the code table. (^ 45)
Blinking on the display:
0001
b
e
a
p
Hz
b
e
a
p
Hz
100 %
C0011
T
= t
⋅
ir
ir
f 2 − f 1
t
= acceleration time wanted
ir
C0011
T
= t
⋅
if
if
f 2 − f 1
t
= deceleration time wanted
if
b
e
a
p
Hz
Set the DIP switch on the standard-I/O to the same
b
e
a
range (see Mounting Instructions for the
p
Hz
standard-I/O)
See motor nameplate
Enter the value for the motor connection type
(star/delta) selected!
Enter the value for the motor connection type
(star/delta) selected!
ALL