Vector control

The following instructions apply to controllers equipped with a standard−I/O function module and
a three−phase AC motor which has been selected according to a power−based assignment.
Switch−on sequence
1.
Connect keypad
2.
Ensure that controller inhibit is active after mains
connection
3.
Switch on the mains
4.
The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)
5.
6.
Go to the ALL menu
Change to the f mode to configure the basic settings for
7.
your drive
8.
Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation
9.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
10.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
11.
Set the acceleration time T
Lenze setting: 5.00 s
12.
Set the deceleration time T
Lenze setting: 5.00 s
13.
Activate the operating mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
14.
Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
EDK82EV222 DE/EN/FR 13.0
Parameter setting with E82ZBC keypad
(C0012)
ir
(C0013)
if
l
Commissioning
Vector control
Comment
Terminal X3/28 = LOW
The USEr menu is active
Blinking on the display: 0050
Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for
the standard I/O)
7