7
Commissioning
Possible settings via DIP switch
ON
1
2
3
The DIP switches on the front serve to set the
ƒ node address (switches 1 ... 6)
ƒ baud rate (switches 7 ... 9)
Switch 10 does not have any function.
The Lenze setting of all DIP switches is OFF.
Note!
Settings via codes
In the Lenze setting (all switches OFF), all values from codes C0350 (node
ƒ
address) and C0351 (baud rate) are accepted.
Changes to codes are accepted by:
ƒ
– A voltage supply switch-off and switch-on or
– A "Reset node" with C0358 = 1
C0350 is inactive if at least one of the switches 1 ... 6 has been set to the
ƒ
ON position before the mains is reconnected.
C0351 is inactive if at least one of the switches 7 ... 9 has been set to the
ƒ
ON position before the mains is reconnected.
Detailed information on the codes is provided in the CAN communication
ƒ
manual and the documentation of the standard device.
EDK82ZAFCC-210 DE/EN/FR 4.0
4
5
6
7
Possible settings via DIP switch
8
9
10
Commissioning
ON
OFF
7
57